Parameter list
Parameters
1-167
Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Description:
Sets the time threshold for the Vdc_min controller (kinetic buffering). If this value is exceeded a fault is output; the
required response can be parameterized .
Prerequisite: p1256 = 1.
Dependency:
Refer to: F07406
Description:
Sets the response for the Vdc_min controller (kinetic buffering).
Values:
0:
Buffer Vdc up to possible failure with undervoltage., n<p1257 -> F7405
1:
Buffer Vdc up to possible failure with undervoltage, n<p1257 -> F7405, t>p1255 -> F7406
Dependency:
Refer to: F07405, F07406
Description:
Sets the speed threshold for the Vdc-min controller (kinetic buffering). If this value is exceeded a fault is output; the
required response can be parameterized .
Description:
Displays the actual output of the Vdc controller (DC link voltage controller)
Description:
Sets the control word for the motor holding brake.
p1255[0...n]
Vdc_min controller time threshold / Vdc_min t_thresh
VECTOR (n/M)
Can be changed:
U, T
Access level:
3
Data type:
Floating Point
Data set:
DDS
Function diagram:
-
P-Group:
Functions
Units group:
TIME
Unit selection:
-
Min Max
Factory
setting
0.000 [s]
10000.000 [s]
0.000 [s]
p1256[0...n]
Vdc_min controller response (kinetic buffering) / Vdc_min response
VECTOR (n/M)
Can be changed:
U, T
Access level:
3
Data type:
Integer16
Data set:
DDS
Function diagram:
-
P-Group:
Functions
Units group:
-
Unit selection:
-
Min Max
Factory
setting
0 1
0
p1257[0...n]
Vdc_min controller speed threshold / Vdc_min n_thresh
VECTOR (n/M)
Can be changed:
U, T
Access level:
3
Data type:
Floating Point
Data set:
DDS
Function diagram:
-
P-Group:
Functions
Units group:
SPEED_ROT
Unit selection:
-
Min Max
Factory
setting
0.0 [1/min]
210000.0 [1/min]
50.0 [1/min]
r1258
CO: Vdc controller output / Vdc_ctrl output
VECTOR (n/M)
Can be changed:
-
Access level:
3
Data type:
Floating Point
Data set:
-
Function diagram:
6220
P-Group:
Functions
Units group:
CURRENT_AC_EFF
Unit selection:
-
Min Max
Factory
setting
- [Aeff]
- [Aeff]
- [Aeff]
p1275
Motor holding brake control word / Brake STW
VECTOR (Extended
brk)
Can be changed:
U, T
Access level:
2
Data type:
Unsigned32
Data set:
-
Function diagram:
-
P-Group:
Functions
Units group:
-
Unit selection:
-
Min Max
Factory
setting
0000 bin
0010 1111 bin
0000 bin