Parameter list
Parameters
1-349
Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Description:
Sets the tolerance time to change over the safety-related input signals (SGE) on the control unit.
A SGE changeover is not simultaneously effective due to the different runtimes in the two monitoring channels.
After an SGE switchover, dynamic data is not subject to a crosswise data comparison during this tolerance time.
Dependency:
Refer to: p9850
Note:
For a crosswise data comparison between p9650 and p9850, a difference of one Safety monitoring clock cycle is
tolerated.
The parameterized time is internally rounded-off to an integer multiple of the monitoring clock cycle.
SGE: Safety-related input signal (e.g. SH terminals)
Description:
Sets the transition period from STOP F to STOP A on the control unit.
Dependency:
Refer to: r9795, p9858
Refer to: F01611
Note:
For a crosswise data comparison between p9658 and p9858, a difference of one Safety monitoring clock cycle is
tolerated.
The parameterized time is internally rounded-off to an integer multiple of the monitoring clock cycle.
STOP F: Defect in a monitoring channel (error in the crosswise data comparison)
STOP A: Pulse cancellation via the safety shutdown path
Description:
Sets the time to carry-out the dynamic update and testing the safety shutdown paths (forced checking procedure).
Within the parameterized time, safe standstill must have been de-selected at least once. The monitoring time is
reset each time that SH is de-selected.
Dependency:
Refer to: A01699
Description:
Enters the Safety Integrated password.
Dependency:
Refer to: F01659
Note:
It is not permissible to change Safety Integrated parameter settings until the Safety Integrated password has been
entered.
p9650
SI tolerance time SGE changeover (control unit) / SI tol SGE_chgovCU
VECTOR
Can be changed:
C2
Access level:
3
Data type:
Floating Point
Data set:
-
Function diagram:
2810
P-Group:
Safety Integrated
Units group:
TIME_M3
Unit selection:
-
Min Max
Factory
setting
0.00 [ms]
2000.00 [ms]
500.00 [ms]
p9658
SI transition time STOP F to STOP A (control unit) / SI STOP F to A CU
VECTOR
Can be changed:
C2
Access level:
3
Data type:
Floating Point
Data set:
-
Function diagram:
2802
P-Group:
Safety Integrated
Units group:
TIME_M3
Unit selection:
-
Min Max
Factory
setting
0.00 [ms]
30000.00 [ms]
0.00 [ms]
p9659
SI timer for the forced checking procedure / SI TimerFrcdCkProc
VECTOR
Can be changed:
C2
Access level:
3
Data type:
Floating Point
Data set:
-
Function diagram:
2810
P-Group:
Safety Integrated
Units group:
TIME_H
Unit selection:
-
Min Max
Factory
setting
0.00 [h]
9000.00 [h]
8.00 [h]
p9761
SI password input / SI password input
VECTOR
Can be changed:
C1, T
Access level:
3
Data type:
Unsigned32
Data set:
-
Function diagram:
2800
P-Group:
Safety Integrated
Units group:
-
Unit selection:
-
Min Max
Factory
setting
0000 hex
FFFF FFFF hex
0000 hex