Picture 2-45 2614 – Missing enable signals
1 = OFF2, enable missing
1
2
3
5
6
8
9
16
17
18
21
22
28
1 = OFF1, enable missing
Meaning
1 = OFF3, enable missing
1 = Enable operation missing
1 = STOP2, enable missing
1 = STOP1, enable missing
1 = EP terminals, enable missing
1 = Infeed, enable missing
1 = OFF1, enable, internal missing
1 = OFF2, enable, internal missing
1 = OFF3, enable, internal missing
1 = STOP2, enable internal missing
1 = STOP1, enable internal missing
1 = Open brake missing
Bit No.
0
r0046
Missing enable signals that prevent the drive going into operation (these can be detected at the ZSW sequence control r0899.2 =
1 [2503]).
- 2614 -
8
7
6
5
4
3
2
1
fp_S01_2614_en.vsd
DO: VECTOR
SINAMICS G
17.12.04
V02.02.00
Sequence control - missing enable signals
0 = Internal fast
stop
[3060.2]
[3060.4]
[3070.2]
[3070.4]
10
11
12
1 = Ramp-function generator enable missing
1 = Ramp-function generator start missing
1 = Setpoint, enable missing
27
1 = De-magnetization not completed
≥
1
Fault with OFF3
response
2000.00 µs
19
1 = Pulse enable, internal missi
n
g
≥
1
1 = Internal RFG missing
[3060.2]
[3070.2]
30
31
1 = Function generator with current input active
1 = Jog setpoint active