Parameters
Parameter list
1-126
Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Description:
Displays fault buffer changes. This counter is incremented every time the fault buffer changes.
Recommenda-
tion:
Used to check whether the fault buffer has been read out consistently.
Dependency:
Refer to: r0945, r0947, r0948, r0949, r2109
Description:
Displays the numbers of faults that have occurred.
Dependency:
Refer to: r0947, r0948, r0949, r2109, r2130, r2133, r2136
Note:
Fault buffer structure (general principle):
r0945[0], r0949[0], r0948[0], r2109[0] --> actual fault case, fault 1
...
r0945[7], r0949[7], r0948[7], r2109[7] --> actual fault case, fault 8
r0945[8], r0949[8], r0948[8], r2109[8] --> 1st acknowledged fault case, fault 1
...
r0945[15], r0949[15], r0948[15], r2109[15] --> 1st acknowledged fault case, fault 8
...
r0945[56], r0949[56], r0948[56], r2109[56] --> 7th acknowledged fault case, fault 1
...
r0945[63], r0949[63], r0948[63], r2109[63] --> 7th acknowledged fault case, fault 8
Description:
Lists the fault codes stored in the drive unit.
Dependency:
The parameter assigned to the fault code is entered in r0951 under the same index.
Refer to: r0951
Description:
This parameter is identical to r0945.
r0944
Counter for fault buffer changes / Fault buff change
All objects
Can be changed:
-
Access level:
2
Data type:
Unsigned16
Data set:
-
Function diagram:
8060
P-Group:
Messages
Units group:
-
Unit selection:
-
Min Max
Factory
setting
- -
-
r0945[0...63]
Fault code / Fault code
All objects
Can be changed:
-
Access level:
2
Data type:
Unsigned16
Data set:
-
Function diagram:
1750,
8060
P-Group:
Messages
Units group:
-
Unit selection:
-
Min Max
Factory
setting
- -
-
r0946[0...65534] Fault code list / Fault code list
All objects
Can be changed:
-
Access level:
3
Data type:
Unsigned16
Data set:
-
Function diagram:
8060
P-Group:
Messages
Units group:
-
Unit selection:
-
Min Max
Factory
setting
- -
-
r0947[0...63]
Fault number / Fault number
All objects
Can be changed:
-
Access level:
3
Data type:
Unsigned16
Data set:
-
Function diagram:
1750,
8060
P-Group:
Messages
Units group:
-
Unit selection:
-
Min Max
Factory
setting
- -
-