Parameters
Parameter list
1-296
Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Description:
Sets the normalization characteristic for the analog inputs of terminal board 30 (TB30).
The normalization characteristic for the analog inputs is defined using two points.
This parameter specifies the y coordinate (percentage) of the 2nd value pair of the characteristic.
Index:
[0] = AI 0 (X482.1/X482.2)
[1] = AI 1 (X482.3/X482.4)
Note:
The parameters for the characteristic do not limit.
Description:
Sets the normalization characteristic for the analog inputs of terminal module 31 (TM31).
The normalization characteristic for the analog inputs is defined using two points.
This parameter specifies the y coordinate (percentage) of the 2nd value pair of the characteristic.
Index:
[0] = AI 0 (X521.1/X521.2, S5.0)
[1] = AI 1 (X521.3/X521.4, S5.1)
Notice:
This parameter is automatically overwritten when the analog input type (p4056) is modified.
Note:
The parameters for the characteristic do not limit.
Description:
Sets the response threshold for wire-breakage monitoring of the analog inputs of terminal module 31 (TM31).
Index:
[0] = AI 0 (X521.1/X521.2, S5.0)
[1] = AI 1 (X521.3/X521.4, S5.1)
Dependency:
Wire-breakage monitoring is active for the following type of analog input: p4056[x] = 3 (unipolar current input moni-
tors 4 mA ... 20 mA).
Refer to: p4056
Description:
Sets the delay time for wire-breakage monitoring of the analog inputs on terminal module 31 (TM31).
p4060[0...1]
TB30 analog inputs, characteristic value y2 / TB30 AI char y2
TB30
Can be changed:
U, T
Access level:
2
Data type:
Floating Point
Data set:
-
Function diagram:
9104
P-Group:
Terminals
Units group:
PERCENT
Unit selection:
-
Min Max
Factory
setting
-1000.00 [%]
1000.00 [%]
100.00 [%]
p4060[0...1]
TM31 analog inputs, characteristic value y2 / TM31 AI char y2
TM31
Can be changed:
U, T
Access level:
2
Data type:
Floating Point
Data set:
-
Function diagram:
9566,
9568
P-Group:
Terminals
Units group:
PERCENT
Unit selection:
-
Min Max
Factory
setting
-1000.00 [%]
1000.00 [%]
100.00 [%]
p4061[0...1]
TM31 analog inputs, wire breakage monitoring response threshold / TM31 WireBrk-
Thresh
TM31
Can be changed:
U, T
Access level:
2
Data type:
Floating Point
Data set:
-
Function diagram:
9566,
9568
P-Group:
Terminals
Units group:
CURRENT_DC_M3
Unit selection:
-
Min Max
Factory
setting
0.00 [mA]
20.00 [mA]
2.00 [mA]
p4062[0...1]
TM31 analog inputs, wire breakage monitoring, delay time / TM31 wirebrk t_del
TM31
Can be changed:
U, T
Access level:
2
Data type:
Unsigned16
Data set:
-
Function diagram:
9566,
9568
P-Group:
Terminals
Units group:
TIME_M3
Unit selection:
-
Min Max
Factory
setting
0 [ms]
1000 [ms]
100 [ms]