![Siemens SINAMICS G List Manual Download Page 188](http://html.mh-extra.com/html/siemens/sinamics-g/sinamics-g_list-manual_378180188.webp)
Parameters
Parameter list
1-188
Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Description:
Sets the upper adaptation speed/velocity of the speed/velocity controller. No adaptation is effective above this
speed/velocity. For P gain, p1460 * p1461 is effective. For the integral action time, p1462 * p1463 is effective.
Dependency:
Refer to: p1460, p1461, p1462, p1463, p1464
Description:
Sets the signal source for the scaling of the P gain of the speed/velocity controller. This also makes the effective P
gain (including adaptations) scalable.
Description:
Displays the effective P gain of the speed controller.
Dependency:
For p0528 = 1, the speed controller gain is represented without any dimensions. In this case, connector output sig-
nal r1468 is increased by a factor of 100 in order to improve the resolution.
Description:
Displays the effective integral action time of the speed/velocity controller.
Description:
Sets the P gain for sensorless operation for the speed/velocity controller.
Dependency:
For VECTOR (r0107) the following applies:
For p0528 = 1, the speed controller gain is represented without any dimensions.
p1465[0...n]
Speed controller adaptation speed, upper / n_ctrl n upper
VECTOR (n/M)
Can be changed:
U, T
Access level:
3
Data type:
Floating Point
Data set:
DDS
Function diagram:
5050,
6050
P-Group:
Control
Units group:
SPEED_ROT
Unit selection:
-
Min Max
Factory
setting
0.00 [1/min]
210000.00 [1/min]
210000.00 [1/min]
p1466[0...n]
CI: Speed controller P-gain scaling / n_ctrl Kp Scal
VECTOR (n/M)
Can be changed:
T
Access level:
3
Data type:
Unsigned32
Data set:
CDS
Function diagram:
5050,
6050
P-Group:
Control
Units group:
-
Unit selection:
-
Min Max
Factory
setting
- -
1
r1468
CO: Speed controller P-gain effective / n_ctrl Kp eff
VECTOR (n/M)
Can be changed:
-
Access level:
3
Data type:
Floating Point
Data set:
-
Function diagram:
6040
P-Group:
Control
Units group:
GAIN_SPEED_CTRL
Unit selection:
p0528
Min Max
Factory
setting
- [Nms/rad]
- [Nms/rad]
- [Nms/rad]
r1469
Speed controller integral action time effective / n_ctrl Tn eff
VECTOR (n/M)
Can be changed:
-
Access level:
3
Data type:
Floating Point
Data set:
-
Function diagram:
5040,
6040
P-Group:
Control
Units group:
TIME_M3
Unit selection:
-
Min Max
Factory
setting
- [ms]
- [ms]
- [ms]
p1470[0...n]
Speed controller sensorless operation P-gain / n_ctrl SLVC Kp
VECTOR (n/M)
Can be changed:
U, T
Access level:
2
Data type:
Floating Point
Data set:
DDS
Function diagram:
5210,
6040,, 6050
P-Group:
Control
Units group:
GAIN_SPEED_CTRL
Unit selection:
p0528
Min Max
Factory
setting
0.000 [Nms/rad]
999999.000 [Nms/rad]
0.300 [Nms/rad]