Parameters
Parameter list
1-294
Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Notice:
For use as voltage input, switch S500 must be set to 0 for the input involved.
Switch S500 is located on the front panel of the TM31 above terminal block X521.
Note:
When changing p4056, the parameters of the normalization characteristic (p4057, p4058, p4059, p4060) are over-
written with the following default values:
For p4056 = 0 or 4, p4057 is set to 0.0 V, p4058 to 0.0 %, p4059 to 10.0 V and p4060 to 100.0 %.
For p4056 = 2 or 3 or 5, p4057 is set to 0.0 mA, p4058 to 0.0 %, p4059 to 20.0 mA and p4060 to 100.0 %.
Description:
Sets the normalization characteristic for the analog inputs of terminal board 30 (TB30).
The normalization characteristic for the analog inputs is defined using two points.
This parameter specifies the x coordinate (input voltage in V) of the 1st value pair of the characteristic.
Index:
[0] = AI 0 (X482.1/X482.2)
[1] = AI 1 (X482.3/X482.4)
Note:
The parameters for the characteristic do not limit.
Description:
Sets the normalization characteristic for the analog inputs of terminal module 31 (TM31).
The normalization characteristic for the analog inputs is defined using two points.
This parameter specifies the x coordinate (input voltage in V or input current in mA) of the 1st value pair of the char-
acteristic.
Index:
[0] = AI 0 (X521.1/X521.2, S5.0)
[1] = AI 1 (X521.3/X521.4, S5.1)
Dependency:
The units of this parameter (V or mA) depend on the analog input type.
Refer to: p4056
Notice:
This parameter is automatically overwritten when the analog input type (p4056) is modified.
Note:
The parameters for the characteristic do not limit.
Description:
Sets the normalization characteristic for the analog inputs of terminal board 30 (TB30).
The normalization characteristic for the analog inputs is defined using two points.
This parameter specifies the y coordinate (percentage) of the 1st value pair of the characteristic.
Index:
[0] = AI 0 (X482.1/X482.2)
[1] = AI 1 (X482.3/X482.4)
Note:
The parameters for the characteristic do not limit.
p4057[0...1]
TB30 analog inputs, characteristic value x1 / TB30 AI char x1
TB30
Can be changed:
U, T
Access level:
2
Data type:
Floating Point
Data set:
-
Function diagram:
9104
P-Group:
Terminals
Units group:
VOLTAGE_AC_PP
Unit selection:
-
Min Max
Factory
setting
-11.000 [V]
11.000 [V]
0.000 [V]
p4057[0...1]
TM31 analog inputs, characteristic value x1 / TM31 AI char x1
TM31
Can be changed:
U, T
Access level:
2
Data type:
Floating Point
Data set:
-
Function diagram:
9566,
9568
P-Group:
Terminals
Units group:
-
Unit selection:
-
Min Max
Factory
setting
-20.000 20.000
0.000
p4058[0...1]
TB30 analog inputs, characteristic value y1 / TB30 AI char y1
TB30
Can be changed:
U, T
Access level:
2
Data type:
Floating Point
Data set:
-
Function diagram:
9104
P-Group:
Terminals
Units group:
PERCENT
Unit selection:
-
Min Max
Factory
setting
-1000.00 [%]
1000.00 [%]
0.00 [%]