Parameter list
Parameters
1-275
Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Description:
Displays the selected and effective fixed value of the technology controller.
Dependency:
Refer to: r2229
Description:
Displays the number of the selected fixed setpoint of the technology controller.
Dependency:
Refer to: r2224
Description:
Sets the configuration for the motorized potentiometer of the technology controller.
Dependency:
Refer to: r2231, p2240
Note:
Re bit 00:
0: The setpoint for the motorized potentiometer is not saved and after ON is entered using p2240.
1: The setpoint for the motorized potentiometer is saved and after ON is entered using p2231.
Re bit 02:
0: Without initial rounding-off
1: With initial rounding-off. The selected ramp-up/down time is correspondingly exceeded.
Description:
Displays the setpoint memory for the motorized potentiometer of the technology controller.
For p2230.0 = 1, the last setpoint that was saved is entered after ON.
Dependency:
Refer to: p2230
r2224
CO: Technology controller, fixed value effective / Tec_ctr FixVal eff
VECTOR (Tech ctrl)
Can be changed:
-
Access level:
2
Data type:
Floating Point
Data set:
-
Function diagram:
7950
P-Group:
Technology
Units group:
PERCENT
Unit selection:
-
Min Max
Factory
setting
- [%]
- [%]
- [%]
r2229
Technology controller current number / Tec_ctrl No. act
VECTOR (Tech ctrl)
Can be changed:
-
Access level:
2
Data type:
Unsigned32
Data set:
-
Function diagram:
7950
P-Group:
Technology
Units group:
-
Unit selection:
-
Min Max
Factory
setting
- -
-
p2230[0...n]
Technology controller motorized potentiometer configuration / Tec_ctr mop config
VECTOR (Tech ctrl)
Can be changed:
U, T
Access level:
3
Data type:
Unsigned32
Data set:
DDS
Function diagram:
7954
P-Group:
Technology
Units group:
-
Unit selection:
-
Min Max
Factory
setting
0000 bin
0111 bin
0110 bin
Bit field:
Bit
Signal name
0 signal
1 signal
FP
00
Data save active
No
Yes
-
02
Initial rounding-off active
No
Yes
-
r2231
Technology controller motorized potentiometer setpoint memory / Tec_ctrl mop
mem
VECTOR (Tech ctrl)
Can be changed:
-
Access level:
2
Data type:
Floating Point
Data set:
-
Function diagram:
7954
P-Group:
Technology
Units group:
PERCENT
Unit selection:
-
Min Max
Factory
setting
- [%]
- [%]
- [%]