Parameters
Parameter list
1-34
Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Dependency:
Refer to: r0002
Note:
The value r0046 = 0 indicates that all enable signals for this drive are present.
Bit 00 = 1 (enable signal missing), if:
- the signal source in p0840 is a 0 signal.
- there is a power-on inhibit.
Bit 01 = 1 (enable signal missing), if:
- the signal source in p0844 or p0845 is a 0 signal.
Bit 02 = 1 (enable signal missing), if:
- the signal source in p0848 or p0849 is a 0 signal.
Bit 03 = 1 (enable signal missing), if:
- the signal source in p0852 is a 0 signal.
Bit 05, bit 06: (being developed)
Bit 08 = 1 (enable signal missing), if:
- the pulse enable via terminal EP at the motor module is missing (X21.3, X21.4).
Bit 09 = 1 (enable signal missing), if:
- the signal source in p0864 is a 0 signal.
Bit 10 = 1 (enable signal missing), if:
- the signal source in p1140 is a 0 signal.
Bit 11 = 1 (enable signal missing) if the speed setpoint is frozen, because:
- the signal source in p1141 is a 0 signal or
- the speed setpoint is entered from jogging and the two signal sources for jogging, bit 0 (p1055) and bit 1 (p1056)
have a 1 signal.
Bit 12 = 1 (enable signal missing), if:
- the signal source in p1142 is a 0 signal.
Bit 16 = 1 (enable signal missing), if:
- there is an OFF1 fault response. The system is only enable if the fault is removed and was acknowledged and the
power-on inhibit withdrawn with OFF1 = 0.
Bit 17 = 1 (enable signal missing), if:
- the commissioning mode is selected (p0009 > 0 or p0010 > 0) or an OFF2 fault response is present.
Bit 18 = 1 (enable signal missing), if:
- OFF3 has still not be completed or an OFF3 fault response is present.
Bit 19 = 1 (internal pulse enable missing), if:
- synchronization is running between the basic clock cycle, DRIVE-CLiQ clock cycle and application clock cycle.
Bit 21 = 1 (enable signal missing), if:
The pulses have been enabled and the speed setpoint has still not been enabled, because:
- the holding brake opening time (p1216) has still not expired.
- The motor has still not been magnetized (induction motor).
Bit 22: Being developed
Bit 27 = 1 (enable signal missing), if:
- de-magnetizing has still not been completed (only for vector).
Bit 28 = 1 (enable signal missing), if:
- the holding brake is closed or has still not been opened.
Bit 31 = 1 (enable signal missing), if:
- the speed setpoint is entered from jogging 1 or 2.
16
OFF1 enable internal missing
No
Yes
-
17
OFF2 enable internal missing
No
Yes
-
18
OFF3 enable internal missing
No
Yes
-
19
Pulse enable internal missing
No
Yes
-
21
STOP2 enable internal missing
No
Yes
-
22
STOP1 enable internal missing
No
Yes
-
27
Demagnetization not completed
No
Yes
-
28
Brake open missing
No
Yes
-
30
Function generator with current input
not active
active
-
31
Jog setpoint active
No
Yes
-