Parameters
Parameter list
1-100
Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Description:
Sets the power module number to which the temperature sensor is connected. The value corresponds to the power
module data set number (Power Data Set, PDS) of the power module. The number power module data sets is
defined in parameter p0120.
Description:
Sets the signal source to evaluate the motor temperature via a BICO interconnection.
Dependency:
Refer to: p0600
Note:
KTY temperature sensor: Valid temperature range -48 °C ... 248 °C.
PTC temperature sensor:
For the -50 °C, the following applies: Motor temperature < nominal response temperature of the PTC.
For the 250 °C, the following applies: Motor temperature >= nominal response temperature of the PTC.
Note:
When using a terminal module 31 (TM31), the following applies:
- the sensor type used is set using p4100.
- the temperature signal is interconnected using CO: r4105.
Description:
Sets the alarm threshold for monitoring the motor temperature.
Note:
The parameter is automatically preset for motors from the motor list (p0301).
Description:
Sets the fault threshold to monitor the motor temperature.
Note:
The parameter is automatically preset for motors from the motor list (p0301).
p0602
Power module number, temperature sensor for parallel circuit configuration / Mot
temp_PM number
VECTOR (Parallel)
Can be changed:
C2, U, T
Access level:
2
Data type:
Unsigned16
Data set:
-
Function diagram:
-
P-Group:
Motor
Units group:
-
Unit selection:
-
Min Max
Factory
setting
0 10
0
p0603
CI: Motor temperature / Mot temperature
VECTOR
Can be changed:
C2, T
Access level:
2
Data type:
Unsigned32
Data set:
-
Function diagram:
8016
P-Group:
Motor
Units group:
-
Unit selection:
-
Min Max
Factory
setting
- -
0
p0604[0...n]
Motor overtemperature alarm threshold / Mot TempAlrmThresh
VECTOR
Can be changed:
C2, U, T
Access level:
2
Data type:
Floating Point
Data set:
MDS
Function diagram:
8016
P-Group:
Motor
Units group:
TEMPERATURE
Unit selection:
-
Min Max
Factory
setting
0.0 [°C]
200.0 [°C]
120.0 [°C]
p0605[0...n]
Motor overtemperature fault threshold / MotTempFaultThresh
VECTOR
Can be changed:
C2, U, T
Access level:
2
Data type:
Floating Point
Data set:
MDS
Function diagram:
8016
P-Group:
Motor
Units group:
TEMPERATURE
Unit selection:
-
Min Max
Factory
setting
0.0 [°C]
200.0 [°C]
155.0 [°C]