Parameters
Parameter list
1-254
Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Dependency:
The alarm buffer is deleted (cleared) by setting p2111 to 0.
Refer to: r2110, r2122, r2123, r2124, r2125
Note:
The parameter is reset to 0 at POWER ON.
Description:
Sets the signal source for external alarm 1.
Dependency:
External alarm 1 --> A07850(F)
Refer to: A07850
Note:
An external alarm is triggered with a 1/0 signal.
Description:
Sets the signal source for external alarm 1.
Dependency:
External alarm 1 --> A07850(F)
Refer to: A07850
Note:
An external alarm is triggered with a 1/0 signal.
Description:
Displays the total system runtime for the drive unit.
Index 0 indicates the system runtime in milliseconds after reaching 86.400.000 ms (24 hours), the value is reset.
Index 1 indicates the system runtime in days.
Dependency:
Refer to: r0948, r2109, r2123, r2125, r2130, r2136, r2145, r2146
Note:
The time in r2114 is used to display the fault and alarm times.
At power-off the counter value is saved.
After the drive unit is powered-up, the counter continues to run with the value that was saved the last time that the
drive unit was powered-down.
Description:
Sets the signal source for external alarm 2.
Dependency:
External alarm 2 --> A07851(F)
Refer to: A07851
Note:
An external alarm is triggered with a 1/0 signal.
p2112
BI: External alarm 1 / External alarm 1
CU, TB30, TM31
Can be changed:
U, T
Access level:
3
Data type:
Unsigned32
Data set:
-
Function diagram:
-
P-Group:
Messages
Units group:
-
Unit selection:
-
Min Max
Factory
setting
- -
1
p2112[0...n]
BI: External alarm 1 / External alarm 1
VECTOR
Can be changed:
U, T
Access level:
3
Data type:
Unsigned32
Data set:
CDS
Function diagram:
2546
P-Group:
Messages
Units group:
-
Unit selection:
-
Min Max
Factory
setting
- -
1
r2114[0...1]
System runtime total / t_System total
CU
Can be changed:
-
Access level:
3
Data type:
Unsigned32
Data set:
-
Function diagram:
-
P-Group:
Messages
Units group:
-
Unit selection:
-
Min Max
Factory
setting
- -
-
p2116
BI: External alarm 2 / External alarm 2
CU, TB30, TM31
Can be changed:
U, T
Access level:
3
Data type:
Unsigned32
Data set:
-
Function diagram:
-
P-Group:
Messages
Units group:
-
Unit selection:
-
Min Max
Factory
setting
- -
1