Parameter list
Parameters
1-195
Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Note:
For vector drives (refer to p0107):
The torque limit is limited to 400% of the rated motor torque.
Description:
Sets the signal source for the upper or torque/force limit when motoring.
Dependency:
p1400 bit 4 = 0: top / bottom
p1400 bit 4 = 1: motoring / regenerating
Refer to: p1520, p1521, p1523
Description:
Sets the signal source for the lower or torque/force limit when regenerating.
Dependency:
p1400 bit 4 = 0: top / bottom
p1400 bit 4 = 1: motoring / regenerating
Refer to: p1520, p1521, p1522
Description:
Sets the scaling for the upper torque limit or the motoring torque limit when motoring.
Dependency:
p1400 bit 4 = 0: top / bottom
p1400 bit 4 = 1: motoring / regenerating
Note:
This parameter can be freely interconnected.
The value has the above significance if it is interconnected from connector input p1528.
Description:
Sets the scaling for the lower torque limit or the torque limit when regenerating.
Dependency:
p1400 bit 4 = 0: top / bottom
p1400 bit 4 = 1: motoring / regenerating
p1522[0...n]
CI: Torque limit, upper/motoring / M_max upper/mot
VECTOR (n/M)
Can be changed:
T
Access level:
3
Data type:
Unsigned32
Data set:
CDS
Function diagram:
1610,
5620, 5630, 6630
P-Group:
Control
Units group:
-
Unit selection:
-
Min Max
Factory
setting
- -
1520[0]
p1523[0...n]
CI: Torque limit, lower/regenerative / M_max lower/regen
VECTOR (n/M)
Can be changed:
T
Access level:
3
Data type:
Unsigned32
Data set:
CDS
Function diagram:
1610,
5620, 5630, 6630
P-Group:
Control
Units group:
-
Unit selection:
-
Min Max
Factory
setting
- -
1521[0]
p1524[0...n]
CO: Torque limit, upper/motoring, scaling / M_max up/mot scal
VECTOR (n/M)
Can be changed:
U, T
Access level:
3
Data type:
Floating Point
Data set:
DDS
Function diagram:
5620,
5630, 6630
P-Group:
Control
Units group:
PERCENT
Unit selection:
-
Min Max
Factory
setting
-2000.0 [%]
2000.0 [%]
100.0 [%]
p1525[0...n]
CO: Torque limit, lower/regenerating scaling / M_max low/gen scal
VECTOR (n/M)
Can be changed:
U, T
Access level:
3
Data type:
Floating Point
Data set:
DDS
Function diagram:
5620,
5630, 6630
P-Group:
Control
Units group:
PERCENT
Unit selection:
-
Min Max
Factory
setting
-2000.0 [%]
2000.0 [%]
100.0 [%]