Parameter list
Parameters
1-313
Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Values:
1:
Square-wave
2:
Staircase
3:
Triangular
4:
Binary noise - PRBS (Pseudo Random Binary Signal)
5:
Sinusoidal
Description:
Sets the period of the signal to be generated for the function generator.
Dependency:
Ineffective when p4820 = 4 (PRBS).
Description:
Sets the pulse width for the signal to be generated for the function generator.
Dependency:
Only effective when p4820 = 1 (square-wave).
Description:
Sets the bandwidth for the signal to be generated for the function generator.
Dependency:
Only effective when p4820 = 4 (PRBS).
Refer to: p4830
Refer to: A02041
Description:
Sets the amplitude for the signal to be generated for the function generator.
Dependency:
Units are dependent on p4810.
If p4810 = 1, 2, 4: the amplitude is referred to p2002 (rated motor current).
If p4810 = 3, 5: the amplitude is referred to p2000 (rated motor speed).
p4821
Function generator period / FG period duration
CU
Can be changed:
U, T
Access level:
3
Data type:
Floating Point
Data set:
-
Function diagram:
-
P-Group:
Trace and function generator
Units group:
TIME_M3
Unit selection:
-
Min Max
Factory
setting
0.00 [ms]
60000.00 [ms]
1000.00 [ms]
p4822
Function generator pulse width / FG pulse width
CU
Can be changed:
U, T
Access level:
3
Data type:
Floating Point
Data set:
-
Function diagram:
-
P-Group:
Trace and function generator
Units group:
TIME_M3
Unit selection:
-
Min Max
Factory
setting
0.00 [ms]
60000.00 [ms]
500.00 [ms]
p4823
Function generator bandwidth / FG bandwith
CU
Can be changed:
U, T
Access level:
3
Data type:
Floating Point
Data set:
-
Function diagram:
-
P-Group:
Trace and function generator
Units group:
FREQUENCY
Unit selection:
-
Min Max
Factory
setting
0.00 [Hz]
16000.00 [Hz]
4000.00 [Hz]
p4824
Function generator amplitude / FG amplitude
CU
Can be changed:
U, T
Access level:
3
Data type:
Floating Point
Data set:
-
Function diagram:
-
P-Group:
Trace and function generator
Units group:
PERCENT
Unit selection:
-
Min Max
Factory
setting
-1600.00 [%]
1600.00 [%]
5.00 [%]