Parameters
Overview of parameters
1-16
Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
The following states may be specified:
Access level (refers only to access via Basic Operator Panel)
Specifies the access level required to be able to display and change the relevant
parameter. The required access level can be set via p0003.
The system uses the following access levels:
1. Standard
2. Extended
3. Expert
4. Service
•
C1
Converter commissioning
C1:
C
ommissioning
1
Converter commissioning is in progress (p0009 > 0).
Pulses cannot be enabled.
A modified parameter value does not take effect until converter com-
missioning mode is exited with p0009 = 0.
•
C2
Drive object commissioning
C2:
C
ommissioning
2
Drive commissioning is in progress (p0009 = 0 and p0010 > 0).
Pulses cannot be enabled.
A modified parameter value does not take effect until drive commis-
sioning mode is exited with p0010 = 0.
•
U
Operation
U: R
u
n
Pulses are enabled.
•
T
Ready
T: Ready
t
o run
Pulses are not enabled and status "C1" or "C2" is not active.
Note:
Parameter p0009 is CU-specific (belongs to control unit).
Parameter p0010 is drive-specific (belongs to each drive object).
The operating status of individual drive objects is displayed in r0002.
Note:
Parameter p0003 is CU-specific (belongs to control unit).