Parameters
Parameter list
1-150
Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Description:
The drive is decelerated from the maximum speed / velocity (p1082) down to standstill (setpoint = 0) in this time.
Dependency:
Refer to: p1082
Description:
Sets the signal source for bypassing the ramp generator (ramp-up and ramp-down times = 0).
Note:
For VECTOR in sensorless operation, it is not permissible that the ramp-function generator is bypassed.
Description:
Sets the initial rounding-off time for the extended ramp generator. The value applies to ramp-up and ramp-down.
Note:
Rounding-off times avoid an abrupt response and prevent damage to the mechanical system.
Description:
Sets the final rounding-off time for the extended ramp generator. The value applies to ramp-up and ramp-down.
Note:
Rounding-off times avoid an abrupt response and prevent damage to the mechanical system.
Description:
Sets the smoothed response to the OFF1 command or the reduced setpoint for the extended ramp-function gener-
ator.
Values:
0:
Cont. smoothing
1:
Discontininuous smoothing
Dependency:
No effect, up to initial rounding-off time p1130) > 0 s.
Note:
Rounding-off is always active for continuous smoothing. Overshoots may occur.
p1121[0...n]
Ramp-function generator ramp-down time / RFG ramp-down time
VECTOR
Can be changed:
C2, U, T
Access level:
1
Data type:
Floating Point
Data set:
DDS
Function diagram:
3060,
3070
P-Group:
Setpoints
Units group:
TIME
Unit selection:
-
Min Max
Factory
setting
0.000 [s]
999999.000 [s]
10.000 [s]
p1122[0...n]
BI: Bypass ramp-function generator / Bypass RFG
VECTOR
Can be changed:
U, T
Access level:
3
Data type:
Unsigned32
Data set:
CDS
Function diagram:
2505
P-Group:
Setpoints
Units group:
-
Unit selection:
-
Min Max
Factory
setting
- -
0
p1130[0...n]
Ramp-function generator initial rounding-off time / RFG t_start_round
VECTOR
Can be changed:
U, T
Access level:
2
Data type:
Floating Point
Data set:
DDS
Function diagram:
3070
P-Group:
Setpoints
Units group:
TIME
Unit selection:
-
Min Max
Factory
setting
0.000 [s]
30.000 [s]
0.000 [s]
p1131[0...n]
Ramp-function generator final rounding-off time / RFG t_end_delay
VECTOR
Can be changed:
U, T
Access level:
2
Data type:
Floating Point
Data set:
DDS
Function diagram:
3070
P-Group:
Setpoints
Units group:
TIME
Unit selection:
-
Min Max
Factory
setting
0.000 [s]
30.000 [s]
0.000 [s]
p1134[0...n]
Ramp-function generator rounding-off type / RFG round-off type
VECTOR
Can be changed:
U, T
Access level:
2
Data type:
Integer16
Data set:
DDS
Function diagram:
3070
P-Group:
Setpoints
Units group:
-
Unit selection:
-
Min Max
Factory
setting
0 1
0