Parameters
Parameter list
1-142
Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Description:
Sets the signal source for the setpoint of the motorized potentiometer in the automatic mode.
Dependency:
Refer to: p1041
Description:
Sets the signal source for the setting command to accept the setting value for the motorized potentiometer.
Dependency:
Refer to: p1044
Description:
Sets the signal source for the setting value for the motorized potentiometer.
Dependency:
Refer to: p1043
Note:
The value becomes effective for a 0/1 edge of the setting command.
Description:
Sets the effective setpoint in front of the internal motorized potentiometer ramp-function generator.
Description:
Sets the ramp-up time for the internal ramp-function generator for the motorized potentiometer.
The setpoint is changed from the zero up to the speed/velocity limit (p1082) within this time (if no initial rounding-off
has been activated).
Dependency:
Refer to: p1030, p1048, p1082
Note:
When the initial rounding-off is activated (p1030.2) the ramp-up time is correspondingly extended.
p1042[0...n]
CI: Motorized potentiometer, automatic setpoint / Mop auto setpoint
VECTOR
Can be changed:
T
Access level:
3
Data type:
Unsigned32
Data set:
CDS
Function diagram:
3020
P-Group:
Setpoints
Units group:
-
Unit selection:
-
Min Max
Factory
setting
- -
0
p1043[0...n]
BI: Motorized potentiometer, accept setpoint / Mop accept set val
VECTOR
Can be changed:
T
Access level:
3
Data type:
Unsigned32
Data set:
CDS
Function diagram:
3020
P-Group:
Setpoints
Units group:
-
Unit selection:
-
Min Max
Factory
setting
- -
0
p1044[0...n]
CI: Motorized potentiometer, setting value / Mop setting value
VECTOR
Can be changed:
T
Access level:
3
Data type:
Unsigned32
Data set:
CDS
Function diagram:
3020
P-Group:
Setpoints
Units group:
-
Unit selection:
-
Min Max
Factory
setting
- -
0
r1045
CO: Motorized potentiometer, speed setpoint in front of the ramp-function generator
/ Mop n_set bef. RFG
VECTOR
Can be changed:
-
Access level:
3
Data type:
Floating Point
Data set:
-
Function diagram:
3020
P-Group:
Setpoints
Units group:
SPEED_ROT
Unit selection:
-
Min Max
Factory
setting
- [1/min]
- [1/min]
- [1/min]
p1047[0...n]
Motorized potentiometer, ramp-up time / Mop ramp-up time
VECTOR
Can be changed:
U, T
Access level:
2
Data type:
Floating Point
Data set:
DDS
Function diagram:
3020
P-Group:
Setpoints
Units group:
TIME
Unit selection:
-
Min Max
Factory
setting
0.000 [s]
1000.000 [s]
10.000 [s]