Safety Integrated
Function diagrams
2-431
Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Picture 2-50 2800 – Parameter manager
- 2800 -
Function diagram
8
7
6
5
4
3
2
1
fp_S01_2800_en.vsd
DO: VECTOR
SINAMICS G
Safety Integrated - parameter manag
e
r
Changing safety parameters
p9601 = 0
[2810.3]
SI password inp
u
t
p9761
Resetting safety parameters
Inhibiting safety functions
x
r9780 CU/r9880 MM
17.12.04
V02.02.00
p9801 = 0
[2810.3]
Safety parameters
p9601 ... p9899
can be reset to the
factory setting using
p0970, p3900
Safety parameters
p9601 ... p9899 can
be changed
SI password new
p9762
SI password, confi
rm
p9763
Safety commissioning
mode [2810.3] [2802.1]
--> select SH
Safety parameterizing enable
y
<1>
<1>
Effective password
=
Password input
=
SET
y = x
Safety parameters
p9601 ... p9899
are valid
=
<1>
<1>
<1> Comparator, refer to [102
1
]
<2> Analog signal memory, refer to [1021]
<3> Reference checksum must be the same as the actual checksum.
p9899
SI reference_
checksum MM
p9898
SI Act_
checksum MM
SI reference_checksum
CU
p9799
SI Act_checks
u
m
CU
p9798
<3>
p0010
≠
95
Safety commissioning
mode exited
=
Checksum
Check for safety
parameters
&
&
&
<2>
Safety Integrated commissioning
p0010 = 95
<3>