Parameters
Parameter list
1-266
Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Dependency:
Refer to: p2153
Description:
Sets the torque/force threshold value for the signal "Torque setpoint < torque threshold value 1" (BO: r2198.10).
Dependency:
Refer to: r2198
Description:
Sets the speed / velocity threshold for the signal "Motor locked" (BO: r2198.6).
Dependency:
Refer to: p2177, r2198
Description:
Sets the delay time for the message "Motor locked" (BO: r2198.6).
If "Motor locked" is identified within this time, then ZSW2.6 is set and an appropriate fault is output.
Dependency:
Refer to: p2175, r2198
Description:
Sets the delay time for the message "Motor stalled" (BO: r2198.7).
If "Motor stalled" is identified within this time, then ZSW2.7 is set and an appropriate fault is output.
Dependency:
Refer to: r2198
Description:
Sets the response when evaluating the load monitoring.
p2174[0...n]
Torque threshold value 1 / M_thresh val 1
VECTOR
Can be changed:
U, T
Access level:
2
Data type:
Floating Point
Data set:
DDS
Function diagram:
8012
P-Group:
Messages
Units group:
TORQUE
Unit selection:
-
Min Max
Factory
setting
0.00 [Nm]
99999.00 [Nm]
5.13 [Nm]
p2175[0...n]
Motor locked speed threshold / Mot lock n_thresh
VECTOR
Can be changed:
U, T
Access level:
3
Data type:
Floating Point
Data set:
DDS
Function diagram:
8012
P-Group:
Messages
Units group:
SPEED_ROT
Unit selection:
-
Min Max
Factory
setting
0.00 [1/min]
210000.00 [1/min]
120.00 [1/min]
p2177[0...n]
Motor locked delay time / Mot lock t_del
VECTOR
Can be changed:
U, T
Access level:
2
Data type:
Floating Point
Data set:
DDS
Function diagram:
8012
P-Group:
Messages
Units group:
TIME
Unit selection:
-
Min Max
Factory
setting
0.000 [s]
65.000 [s]
1.000 [s]
p2178[0...n]
Motor stalled delay time / Mot stall t_del
VECTOR
Can be changed:
U, T
Access level:
3
Data type:
Floating Point
Data set:
DDS
Function diagram:
8012
P-Group:
Messages
Units group:
TIME
Unit selection:
-
Min Max
Factory
setting
0.000 [s]
1.000 [s]
0.010 [s]
p2181[0...n]
Load monitoring, response / Load monit. resp.
VECTOR (Extended
msg)
Can be changed:
U, T
Access level:
3
Data type:
Integer16
Data set:
DDS
Function diagram:
8013
P-Group:
Messages
Units group:
-
Unit selection:
-
Min Max
Factory
setting
0 6
0