![Siemens SINAMICS G List Manual Download Page 417](http://html.mh-extra.com/html/siemens/sinamics-g/sinamics-g_list-manual_378180417.webp)
Internal control/status words
Function diagrams
2-417
Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Picture 2-39 2536 – Status word monitoring functions 2
- 2536 -
8
7
6
5
4
3
2
1
fp_S01_2536_en.vsd
DO: VECTOR
SINAMICS G
17.12.04
V02.02.00
Internal control/status words - status word, monitoring functions 2
p0115[3] (4000.00 µs)
r2198
ZSW monitoring functions 2
r2198.10
r2198.6
r2198.7
11
12
13
14
15
Reserved
Status word, monitoring functions
2
Reserved
Reserved
Reserved
1 = |n_set| < p2161
1 = n_set > 0
1 = Motor locked
1 = Motor stalled
Reserved
Reserved
1 = Torque setpoint < toque threshold value 1 (p2174)
1 = Load monitoring signals an alarm
1 = Load monitoring signals a fault
Reserved
Reserved
Reserved
9
10
8
6
5
4
3
2
1
0
Bit No.
r2198.5
7
From speed signals [8010.8]
From speed signals [8010.8]
From torque signals, motor locked/stalled [8012.8]
From torque signals, motor locked/stalled [8012.8]
From torque signals, motor locked/stalled [8012.3]
From load monitoring [8013.8]
From load monitoring [8013.8]
r2198.11
r2198.12
r2198.4
<1>
Only for activated function module "expanded
messages/monitoring functions" (r0108.17 = 1).
<1>
<1>
Function diagram