Parameter list
Parameters
1-149
Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Description:
Sets the signal source to reverse the motor direction (of rotation).
Dependency:
Refer to: r1198
Description:
Displays the speed/velocity setpoint after the changeover and limiting the direction.
Description:
Sets the ramp-function generator type.
Values:
0:
Basic ramp-function generator
1:
Extended ramp-function generator
Note:
Another ramp-function generator type can only be selected when the motor is at a standstill.
Description:
Displays the setpoint at the input of the ramp-function generator.
Note:
The setpoint is influenced by other functions, e.g. skip (suppressed) speeds, minimum and maximum limits.
Description:
The drive is accelerated from standstill (setpoint = 0) up to the maximum speed/velocity (p1082) in this time.
Dependency:
Refer to: p1082
p1113[0...n]
BI: Direction reversal / Direction reversal
VECTOR
Can be changed:
T
Access level:
3
Data type:
Unsigned32
Data set:
CDS
Function diagram:
2442,
2505
P-Group:
Setpoints
Units group:
-
Unit selection:
-
Min Max
Factory
setting
- -
0
r1114
CO: Setpoint after the direction of rotation limit / Setpt after limit
VECTOR
Can be changed:
-
Access level:
3
Data type:
Floating Point
Data set:
-
Function diagram:
1550,
3040, 3050
P-Group:
Setpoints
Units group:
SPEED_ROT
Unit selection:
-
Min Max
Factory
setting
- [1/min]
- [1/min]
- [1/min]
p1115
Ramp-function generator selection / RFG selection
VECTOR
Can be changed:
T
Access level:
3
Data type:
Integer16
Data set:
-
Function diagram:
1550,
3080
P-Group:
Setpoints
Units group:
-
Unit selection:
-
Min Max
Factory
setting
0 1
0
r1119
CO: Ramp-function generator setpoint at the input / RFG setpt at input
VECTOR
Can be changed:
-
Access level:
3
Data type:
Floating Point
Data set:
-
Function diagram:
1550,
1750, 3050, 3060, 3070, 8010
P-Group:
Setpoints
Units group:
SPEED_ROT
Unit selection:
-
Min Max
Factory
setting
- [1/min]
- [1/min]
- [1/min]
p1120[0...n]
Ramp-function generator ramp-up time / RFG ramp-up time
VECTOR
Can be changed:
C2, U, T
Access level:
1
Data type:
Floating Point
Data set:
DDS
Function diagram:
3060,
3070
P-Group:
Setpoints
Units group:
TIME
Unit selection:
-
Min Max
Factory
setting
0.000 [s]
999999.000 [s]
10.000 [s]