Parameter list
Parameters
1-31
Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Note:
SERVO: Smoothing time constant = 100 ms
VECTOR: Smoothing time constant = 300 ms
The signal is not suitable as process quantity and may only be used as display quantity.
The following applies for SERVO:
The torque-generating current actual value is available smoothed (r0030 with 100 ms, r0078[1] with p0045) and
unsmoothed (r0078[0]).
The following applies for VECTOR:
The torque-generating current actual value is available smoothed (r0030 with 300 ms) and unsmoothed (r0078).
Description:
Displays the smoothed torque/force actual value.
Dependency:
Refer to: r0080
Note:
Smoothing time constant = 100 ms
The signal is not suitable as process quantity and may only be used as display quantity.
The active current actual value is available smoothed (r0031) and unsmoothed (r0080).
Description:
Displays the smoothed actual value of the active power.
Dependency:
Refer to: r0082
Note:
Significance for the drive: Power output at the motor shaft
Significance for the infeed: Power consumed
For A_INF, the following applies:
The active power is available smoothed (r0032 with 300 ms) and unsmoothed (r0082).
The following applies for SERVO:
The active power is available smoothed (r0032 with 100 ms, r0082[1] with p0045) and unsmoothed (r0082[0]).
For VECTOR, the following applies:
The active power is available smoothed (r0032 with 100 ms) and unsmoothed (r0082).
Description:
Displays the smoothed torque/force utilization as a percentage.
The torque/force utilization is obtained from the required smoothed torque/force referred to the torque/force limit.
Dependency:
Refer to: r0081
r0031
Actual torque smoothed / M_act smooth
VECTOR
Can be changed:
-
Access level:
2
Data type:
Floating Point
Data set:
-
Function diagram:
5730
P-Group:
Displays, signals
Units group:
TORQUE
Unit selection:
-
Min Max
Factory
setting
- [Nm]
- [Nm]
- [Nm]
r0032
Power factor, smoothed / Power factor smth
VECTOR
Can be changed:
-
Access level:
2
Data type:
Floating Point
Data set:
-
Function diagram:
5730,
6714, 8950
P-Group:
Displays, signals
Units group:
POWER_P3
Unit selection:
-
Min Max
Factory
setting
- [kW]
- [kW]
- [kW]
r0033
Torque utilization, smoothed / M_util smooth
VECTOR
Can be changed:
-
Access level:
3
Data type:
Floating Point
Data set:
-
Function diagram:
8012
P-Group:
Displays, signals
Units group:
PERCENT
Unit selection:
-
Min Max
Factory
setting
- [%]
- [%]
- [%]