Parameter list
Parameters
1-33
Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Index:
[0] = Maximum inverter
[1] = Maximum depletion layer
[2] = Maximum rectifier
[3] = Air intake
[4] = Electronics unit in the power module
[5] = Inverter 1
[6] = Inverter 2
[7] = Inverter 3
[8] = Inverter 4
[9] = Inverter 5
[10] = Inverter 6
[11] = Rectifier 1
[12] = Rectifier 2
[13] = Depletion layer 1
[14] = Depletion layer 2
[15] = Depletion layer 3
[16] = Depletion layer 4
[17] = Depletion layer 5
[18] = Depletion layer 6
Dependency:
Refer to: p0290
Description:
Displays the smoothed actual power factor.
Note:
Smoothing time constant: 100 ms (for active line module and vector drive: 300 ms)
The signal is not suitable as process quantity and may only be used as display quantity.
Significance for the motor: Motor power factor
Significance for the infeed: Power factor at the connection point (p3470, p3471)
Description:
Displays missing enable signals that are preventing the closed-loop drive control from being commissioned.
r0038
Power factor, smoothed / CosPhi smooth
VECTOR
Can be changed:
-
Access level:
3
Data type:
Floating Point
Data set:
-
Function diagram:
8950
P-Group:
Displays, signals
Units group:
-
Unit selection:
-
Min Max
Factory
setting
- -
-
r0046
CO/BO: Missing drive enable signals / Drv miss enable
VECTOR
Can be changed:
-
Access level:
1
Data type:
Unsigned32
Data set:
-
Function diagram:
2614
P-Group:
Displays, signals
Units group:
-
Unit selection:
-
Min Max
Factory
setting
- -
-
Bit field:
Bit
Signal name
0 signal
1 signal
FP
00
OFF1 enable missing
No
Yes
-
01
OFF2 enable missing
No
Yes
-
02
OFF3 enable missing
No
Yes
-
03
Enable run missing
No
Yes
-
05
STOP2 enable missing
No
Yes
-
06
STOP1 enable missing
No
Yes
-
08
EP terminals enable missing
No
Yes
-
09
Infeed enable missing
No
Yes
-
10
Ramp-function generator enable missing
No
Yes
-
11
Ramp-function generator start missing
No
Yes
-
12
Setpoint enable missing
No
Yes
-