Parameters
Parameter list
1-250
Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Notice:
It is not possible to re-parameterize the fault response to a fault in the following cases:
- if there is no existing fault number.
- the message type is not "fault" (F).
- when a fault is present.
Description:
Sets the fault response for the selected fault.
Values:
0:
NONE
1:
OFF1
2:
OFF2
3:
OFF3
4:
STOP1 (being developed)
5:
STOP2
6:
DCBRAKE (being developed)
7:
ENCODER (p0491)
Dependency:
The fault is selected and the required response is set under the same index.
Refer to: p2100
Notice:
It is not possible to re-parameterize the response to a specific fault for faults that are already present (queued).
Note:
OFF1:
Braking along the ramp-function generator down ramp followed by a pulse inhibit.
OFF2:
Internal/external pulse inhibit.
OFF3:
Braking along the OFF3 down ramp followed by a pulse inhibit.
STOP2:
n_set = 0
The fault response can only be changed for faults with the appropriate identification.
Example:
F12345 and fault response = NONE (OFF1, OFF2) --> The NONE fault response can be changed to either OFF1 or
OFF2.
Description:
Sets the first signal source to acknowledge faults.
Note:
A fault acknowledgment is triggered with a 0/1 signal.
p2101[0...19]
Setting the fault response / Fault response
All objects
Can be changed:
U, T
Access level:
3
Data type:
Integer16
Data set:
-
Function diagram:
1750,
8075
P-Group:
Messages
Units group:
-
Unit selection:
-
Min Max
Factory
setting
0 7
0
p2103
BI: 1. Acknowledge faults / 1. Acknowledge
CU, TB30, TM31
Can be changed:
U, T
Access level:
3
Data type:
Unsigned32
Data set:
-
Function diagram:
-
P-Group:
Messages
Units group:
-
Unit selection:
-
Min Max
Factory
setting
- -
0