Parameters
Parameter list
1-116
Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Description:
Displays what has the master control.
The drive can be controlled via the BICO interconnection or from external (e.g. the commissioning software).
Dependency:
Refer to: p0806
Note:
Bit 0 = 0: BICO interconnection active
Bit 0 = 1: Master control for PC/AOP
The master control is used from the commissioning software (drive control panel) and from the advanced operator
panel (AOP, local mode).
Description:
Copies one command data set (CDS) into another.
Index:
[0] = Source Command Data Set
[1] = Target command data set
[2] = Start copying
Note:
Procedure:
1. In Index 0, enter which command data set should be copied.
2. In Index 1, enter the command data set that is to be copied into.
3. Start copying: Set index 2 from 0 to 1.
p0809[2] is automatically set to 0 when copying is completed.
Description:
Sets the signal source to select the command data set bit 0 (CDS bit 0).
Dependency:
Refer to: r0050, p0811, p0812, p0813, r0836
Note:
Command data sets are selected using the binector inputs p0810, p0811, p0812 and p0813.
For a command data set, selected using the binector inputs, is displayed in r0836.
The currently effective command data set is displayed in r0050.
A command data set can be copied using p0809.
r0807
BO: Master control active / PcCtrl active
VECTOR
Can be changed:
-
Access level:
2
Data type:
Unsigned8
Data set:
-
Function diagram:
-
P-Group:
Displays, signals
Units group:
-
Unit selection:
-
Min Max
Factory
setting
- -
-
Bit field:
Bit
Signal name
0 signal
1 signal
FP
00
Master control active
No
Yes
5030
p0809[0...2]
Copy command data set CDS / Copy CDS
VECTOR
Can be changed:
T
Access level:
2
Data type:
Unsigned8
Data set:
-
Function diagram:
-
P-Group:
Commands
Units group:
-
Unit selection:
-
Min Max
Factory
setting
0 15
0
p0810
BI: Command data set selection CDS bit 0 / CDS select., bit 0
VECTOR
Can be changed:
T
Access level:
3
Data type:
Unsigned32
Data set:
-
Function diagram:
2578,
8920
P-Group:
Commands
Units group:
-
Unit selection:
-
Min Max
Factory
setting
- -
0