Parameters
Parameter list
1-290
Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Description:
Sets the signal source for terminal DI/DO 11 (X541.5) of terminal module 31 (TM31).
Note:
DI/DO: Bidirectional digital input/output
Prerequisite: The DI/DO must be set as an output (p4028.11 = 1).
Description:
Sets the limit for the total output voltage of terminals X541.1, X541.2, X541.3 and X541.4 (DI/DO 8 ... 11) of termi-
nal module 31 (TM31).
Values:
0:
0.1 A total current limit DI/DO 8 ... 11
1:
1.0 A total current limit DI/DO 8 ... 11
Dependency:
Refer to: p4028
Warning!
Since the sum of the output currents at terminals X541.1, X541.2, X541.3 and X541.4 is limited, an overcurrent or
short circuit at one output terminal can cause a dip in the signal at the other terminals.
Description:
Displays the status of the digital outputs of the terminal board 30 (TB30).
Note:
DO: Digital output
Inversion using p4048 has been taken into account.
Description:
Displays the status of the digital outputs of terminal module 31 (TM31).
p4041
BI: TM31 signal source for terminal DI/DO 11 / TM31 S_src DI/DO11
TM31
Can be changed:
U, T
Access level:
1
Data type:
Unsigned32
Data set:
-
Function diagram:
1840,
9562
P-Group:
Commands
Units group:
-
Unit selection:
-
Min Max
Factory
setting
- -
0
p4046
TM31 digital outputs, limit current / TM31 DO limit curr
TM31
Can be changed:
T
Access level:
2
Data type:
Integer16
Data set:
-
Function diagram:
9560
P-Group:
Commands
Units group:
-
Unit selection:
-
Min Max
Factory
setting
0 1
0
r4047
TB30 digital outputs status / TB30 DO status
TB30
Can be changed:
-
Access level:
1
Data type:
Unsigned32
Data set:
-
Function diagram:
9102
P-Group:
Commands
Units group:
-
Unit selection:
-
Min Max
Factory
setting
- -
-
Bit field:
Bit
Signal name
0 signal
1 signal
FP
00
DO 0 (X481.5)
Low
High
-
01
DO 1 (X481.6)
Low
High
-
02
DO 2 (X481.7)
Low
High
-
03
DO 3 (X481.8)
Low
High
-
r4047
TM31 digital outputs status / TM31 DO status
TM31
Can be changed:
-
Access level:
1
Data type:
Unsigned32
Data set:
-
Function diagram:
9556,
9560, 9562
P-Group:
Commands
Units group:
-
Unit selection:
-
Min Max
Factory
setting
- -
-