Parameters
Parameter list
1-122
Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Description:
Sets the signal source for the command "unconditionally open holding brake".
Description:
Sets the signal source for the command "enable speed controller" (r0898.12).
Dependency:
Refer to: r0898
Note:
0 signal: Set the I component and speed controller output to zero.
1 signal: Enable the speed controller.
Description:
Sets the monitoring time for the power module.
The monitoring time is started after an 0/1 edge of the ON/OFF1 command. If the power module does not output a
READY feedback signal within this time, then the appropriate message is output.
The monitoring time includes, if required, the time to pre-charge the DC link and the de-bounce time of the contac-
tors.
Dependency:
Refer to: F06000, F07802
Note:
The pre-assignment (default) value and the maximum value of this parameter are dependent on the power rating
class and the type of construction (design) of the power module.
Description:
Sets the signal source for the feedback signal from the line contactor.
Recommenda-
tion:
For activated monitoring (BI: p0860 not equal to r0863.1) to control the line line contactor, the signal BO: r0863.1 of
the particular drive object should be used.
Dependency:
Refer to: p0861, r0863
Refer to: F07300
Notice:
The line contactor monitoring is de-activated if the control signal of the particular drive object is set as the signal
source for the feedback signal of the line contactor (BI: p0860 = r0863.1).
p0855[0...n]
BI: Unconditionally release holding brake / Uncond. open brake
VECTOR
Can be changed:
T
Access level:
3
Data type:
Unsigned32
Data set:
CDS
Function diagram:
2701
P-Group:
Commands
Units group:
-
Unit selection:
-
Min Max
Factory
setting
- -
0
p0856[0...n]
BI: Enable speed controller / Enable n_ctrl
VECTOR
Can be changed:
T
Access level:
3
Data type:
Unsigned32
Data set:
CDS
Function diagram:
2501
P-Group:
Commands
Units group:
-
Unit selection:
-
Min Max
Factory
setting
- -
1
p0857
Power module monitoring time / PM t_monit
VECTOR
Can be changed:
T
Access level:
2
Data type:
Floating Point
Data set:
-
Function diagram:
2610,
8932, 8964
P-Group:
Commands
Units group:
TIME_M3
Unit selection:
-
Min Max
Factory
setting
2000.0 [ms]
60000.0 [ms]
6000.0 [ms]
p0860
BI: Line contactor, feedback signal / Line contact feedb
VECTOR
Can be changed:
T
Access level:
3
Data type:
Unsigned32
Data set:
-
Function diagram:
8932,
8934
P-Group:
Commands
Units group:
-
Unit selection:
-
Min Max
Factory
setting
- -
863.1