Appendix G: PX3 Models with Residual Current Monitoring
807
To disable this function, deselect the "Perform RCM self-test"
checkbox.
To enable this function, select the "Perform RCM self-test"
checkbox.
3.
Click Save.
Setting RCM DC Current Thresholds
RCM DC current sensors are available on Type B models only. See
RCM Current Sensor
(on page 797).
You can also configure upper thresholds for RCM DC current sensors so
that an alarm will be displayed on the page of
Dashboard
(on page 160)
when RCM DC sensors enter an alerted state.
To configure RCM DC's upper thresholds:
1.
Click Inlet to open the Inlet page.
2.
Click the Thresholds title bar at the bottom of the page to display
inlet thresholds.
3.
Click the desired sensor (required), and then click Edit Thresholds.
For example, select "L1 Residual DC Current".
4.
Make changes as needed.