Chapter 8: Using the Command Line Interface
668
config:#
sensor outlet <n> <sensor type> lowerCritical <option>
Set the Lower Warning threshold for an outlet sensor:
config:#
sensor outlet <n> <sensor type> lowerWarning <option>
Set the deassertion hysteresis for an outlet sensor:
config:#
sensor outlet <n> <sensor type> hysteresis <hy_value>
Set the assertion timeout for an outlet sensor:
config:#
sensor outlet <n> <sensor type> assertionTimeout <as_value>
Variables:
<n> is the number of the outlet that you want to configure.
<sensor type> is one of the following sensor types:
Sensor type
Description
current Current
sensor
voltage Voltage
sensor
activePower Active
power
sensor
apparentPower
Apparent power sensor
powerFactor Power
factor
sensor
activeEnergy
Active energy sensor
lineFrequency Line
frequency sensor
Note: If the requested sensor type is not supported, the "Sensor is
not available" message is displayed.
<option> is one of the options:
enable, disable or a numeric value.
Option
Description
enable
Enables the specified threshold for a specific
outlet sensor.
disable Disables
the
specified threshold for a specific
outlet sensor.
Summary of Contents for Raritan PX3-3000 Series
Page 5: ......
Page 90: ...Chapter 4 Connecting External Equipment Optional 69 ...
Page 424: ...Chapter 6 Using the Web Interface 403 ...
Page 447: ...Chapter 6 Using the Web Interface 426 ...
Page 448: ...Chapter 6 Using the Web Interface 427 Continued ...
Page 885: ...Appendix K RADIUS Configuration Illustration 864 Note If your PX3 uses PAP then select PAP ...
Page 890: ...Appendix K RADIUS Configuration Illustration 869 14 The new attribute is added Click OK ...
Page 891: ...Appendix K RADIUS Configuration Illustration 870 15 Click Next to continue ...
Page 921: ...Appendix L Additional PX3 Information 900 ...