Chapter 8: Using the Command Line Interface
707
Restarting the PDU
This command restarts the PX3. It is not a factory default reset.
To restart the PX3:
1.
Ensure you have entered administrator mode and the # prompt is
displayed.
2.
Type either of the following commands to restart the PX3.
#
reset unit
-- OR --
#
reset unit
/y
3.
If you entered the command without "
/y
" in Step 2, a message
appears prompting you to confirm the operation. Type y to confirm
the reset.
4.
Wait until the reset is complete.
Note: Device reset will cause CLI communications over an "USB"
connection to be lost. Therefore, re-connect the USB cable after the
reset is complete.
Resetting Active Energy Readings
You can reset either one active energy sensor or all active energy
sensors at a time to restart the energy accumulation process.
Only users with the "Admin" role assigned can reset active energy
readings.
To reset all active energy readings of the PX3:
#
reset activeEnergy pdu
-- OR --
#
reset activeEnergy pdu /y
To reset one inlet's active energy readings:
#
reset activeEnergy inlet <n>
-- OR --
#
reset activeEnergy inlet <n> /y
To reset one outlet's active energy readings:
#
reset activeEnergy outlet <outlet_n>
-- OR --
Summary of Contents for Raritan PX3-3000 Series
Page 5: ......
Page 90: ...Chapter 4 Connecting External Equipment Optional 69 ...
Page 424: ...Chapter 6 Using the Web Interface 403 ...
Page 447: ...Chapter 6 Using the Web Interface 426 ...
Page 448: ...Chapter 6 Using the Web Interface 427 Continued ...
Page 885: ...Appendix K RADIUS Configuration Illustration 864 Note If your PX3 uses PAP then select PAP ...
Page 890: ...Appendix K RADIUS Configuration Illustration 869 14 The new attribute is added Click OK ...
Page 891: ...Appendix K RADIUS Configuration Illustration 870 15 Click Next to continue ...
Page 921: ...Appendix L Additional PX3 Information 900 ...