Chapter 5: Introduction to PDU Components
143
To replace a fuse on 1U PDUs:
1.
Disconnect the PDU's power cord from the power source.
2.
Remove the desired fuse from the PDU's fuse carrier using a flat
screwdriver.
a.
Rotate the fuse knob counterclockwise until its slot is inclined to
45 degrees.
b.
Take this knob out of the fuse carrier.
3.
Remove the original fuse from this knob, and insert either end of a
new one into the knob. Make sure the new fuse's rating is the same
as the original one.
Number
Description
Fuse knob
Fuse
4.
Install this knob along with the new fuse into the fuse carrier using a
flat screwdriver.
a.
Have this knob's slot inclined 45 degrees when inserting the
knob into the fuse carrier.
b.
Gently push this knob into the fuse carrier and then rotate it
clockwise until its slot is horizontal.
Summary of Contents for Raritan PX3-3000 Series
Page 5: ......
Page 90: ...Chapter 4 Connecting External Equipment Optional 69 ...
Page 424: ...Chapter 6 Using the Web Interface 403 ...
Page 447: ...Chapter 6 Using the Web Interface 426 ...
Page 448: ...Chapter 6 Using the Web Interface 427 Continued ...
Page 885: ...Appendix K RADIUS Configuration Illustration 864 Note If your PX3 uses PAP then select PAP ...
Page 890: ...Appendix K RADIUS Configuration Illustration 869 14 The new attribute is added Click OK ...
Page 891: ...Appendix K RADIUS Configuration Illustration 870 15 Click Next to continue ...
Page 921: ...Appendix L Additional PX3 Information 900 ...