Chapter 8: Using the Command Line Interface
557
Setting the Outlet Power-On Sequence Delay
This section applies to outlet-switching capable models only.
This command sets the delays (in seconds) for outlets when turning on
all outlets in sequence.
config:#
pdu outletSequenceDelay <outlet1>:<delay1>;<outlet2>:<delay2>;
<outlet3>:<delay3>;...
Separate outlet numbers and their delay settings with a colon. Outlets
followed by delays are separated with a semicolon.
Variables:
<outlet1>, <outlet2>, <outlet3> and the like are individual outlet
numbers or a range of outlets using a dash. For example,
3-8
represents outlets 3 to 8.
<delay1>, <delay2>, <delay3> and the like are the delay time in
seconds.
Note: Power-on sequencing is disabled in the latching mode. See
PX3
Latching Relay Behavior
(on page 178).
Setting the PDU-Defined Default Outlet State
This section applies to outlet-switching capable models only.
This command determines the initial power condition of all outlets after
powering up the PDU.
config:#
pdu outletStateOnDeviceStartup <option>
Variables:
<option> is one of the options:
off, on or lastKnownState.
Option
Description
off
Switches OFF all outlets when the PX3 powers up.
on
Switches ON all outlets when the PX3 powers up.
Summary of Contents for Raritan PX3-3000 Series
Page 5: ......
Page 90: ...Chapter 4 Connecting External Equipment Optional 69 ...
Page 424: ...Chapter 6 Using the Web Interface 403 ...
Page 447: ...Chapter 6 Using the Web Interface 426 ...
Page 448: ...Chapter 6 Using the Web Interface 427 Continued ...
Page 885: ...Appendix K RADIUS Configuration Illustration 864 Note If your PX3 uses PAP then select PAP ...
Page 890: ...Appendix K RADIUS Configuration Illustration 869 14 The new attribute is added Click OK ...
Page 891: ...Appendix K RADIUS Configuration Illustration 870 15 Click Next to continue ...
Page 921: ...Appendix L Additional PX3 Information 900 ...