Chapter 6: Using the Web Interface
415
Any sensor reading or state returns to normal.
Any sensor becomes unavailable.
The active energy sensor is reset.
For example, when the Inlet I1's voltage exceeds the upper warning
threshold, the SNMP notifications are sent, and when the voltage
drops below the upper warning threshold, the SNMP notifications are
sent again.
Sample Environmental-Sensor-Level Event Rule
This section applies to outlet-switching capable models only.
In this example, we want PX3 to activate the load shedding function when
a contact closure sensor enters the alarmed state. This event rule
requires creating a new action before creating the rule.
Step 1: create a new action for activating the load shedding
1.
Choose Device Settings > Event Rules >
.
2.
In this illustration, assign the name "Activate Load Shedding" to the
new action.
3.
In the Action field, select "Change load shedding state."
4.
In the Operation field, select "Start load shedding."
5.
Click Create to finish the creation.
Summary of Contents for Raritan PX3-3000 Series
Page 5: ......
Page 90: ...Chapter 4 Connecting External Equipment Optional 69 ...
Page 424: ...Chapter 6 Using the Web Interface 403 ...
Page 447: ...Chapter 6 Using the Web Interface 426 ...
Page 448: ...Chapter 6 Using the Web Interface 427 Continued ...
Page 885: ...Appendix K RADIUS Configuration Illustration 864 Note If your PX3 uses PAP then select PAP ...
Page 890: ...Appendix K RADIUS Configuration Illustration 869 14 The new attribute is added Click OK ...
Page 891: ...Appendix K RADIUS Configuration Illustration 870 15 Click Next to continue ...
Page 921: ...Appendix L Additional PX3 Information 900 ...