Appendix L: Additional PX3 Information
903
Threshold
Default value
Hysteresis 1A
Multi-phase inlets or outlets:
Line-Line RMS voltage:
Threshold
Default value
Lower critical
-6% of minimum rating
Lower warning
-3% of minimum rating
Upper warning
+3% of maximum rating
Upper critical
+6% of maximum rating
Hysteresis 2V
Line RMS current:
Threshold
Default value
Upper warning
65% of rating
Upper critical
80% of rating
Hysteresis 1A
Unbalanced current:
Threshold
Default value
Upper critical
10% -- disabled by default
Upper warning
5% -- disabled by default
Hysteresis 2%
Overcurrent protectors which aims to protect the PDU's outlets:
OCP RMS current:
Threshold
Default value
Upper critical
80% of OCP rating