Chapter 8: Using the Command Line Interface
536
Inlet Pole Sensor Threshold Information
This command is only available for a three-phase PDU except for an
in-line monitor (PX3-3000 series).
This command syntax shows the specified inlet pole sensor's
threshold-related information.
#
show sensor inletpole <n> <p> <sensor type>
To show detailed information, add the parameter "details" to the end of
the command.
#
show sensor inletpole <n> <p> <sensor type>
details
Variables:
<n> is the number of the inlet whose pole sensors you want to query.
For a single-inlet PDU, <n> is always 1.
<p> is the label of the inlet pole whose sensors you want to query.
Pole
Label
<p>
Current sensor
Voltage sensor
1
L1
L1
L1 - L2
2
L2
L2
L2 - L3
3
L3
L3
L3 - L1
<sensor type> is one of the following sensor types:
Sensor type
Description
current Current
sensor
voltage Voltage
sensor
activePower Active
power
sensor
apparentPower
Apparent power sensor
powerFactor Power
factor
sensor
activeEnergy
Active energy sensor
Summary of Contents for Raritan PX3-3000 Series
Page 5: ......
Page 90: ...Chapter 4 Connecting External Equipment Optional 69 ...
Page 424: ...Chapter 6 Using the Web Interface 403 ...
Page 447: ...Chapter 6 Using the Web Interface 426 ...
Page 448: ...Chapter 6 Using the Web Interface 427 Continued ...
Page 885: ...Appendix K RADIUS Configuration Illustration 864 Note If your PX3 uses PAP then select PAP ...
Page 890: ...Appendix K RADIUS Configuration Illustration 869 14 The new attribute is added Click OK ...
Page 891: ...Appendix K RADIUS Configuration Illustration 870 15 Click Next to continue ...
Page 921: ...Appendix L Additional PX3 Information 900 ...