background image

HP Modular Power Distribution 

Unit Kit 

Installation Instructions 

 

 

 

 

 

 

Overview 

These installation instructions are provided to assist qualified 
personnel with the installation of the HP Modular Power Distribution 

Unit (mPDU) Kit. 

The input voltage of a single phase mPDU is either 100 to 127 VAC 
or 200 to 240 VAC, depending on the model. 

The input voltage of a three phase mPDU is 200 to 240 VAC, phase-

phase or phase-neutral, depending on the model. 

The control unit (if included) provides the following features: 

 

Flexible mounting in 0U or 1U configurations, maximizing rack 
space (no additional parts are required for mounting) 

 

Overcurrent and short-circuit protection for each output (UL-
489-listed circuit breakers) 

 

Manual on/off control for each of the output load groups 

 

Pilot light for main AC input (depending on the model) 

 

IEC-320 C19 outlets to power extension bars or other IEC-320 
C20 plug-compatible equipment 

 

Easy identification and reset of overload circuits (circuit 
breakers move to Off position), minimizing downtime 

 

Power cord retention 

 

Recessed handles to prevent inadvertent power-off 

The extension bars (if included) provide the following features: 

 

Multiple power outlets, conveniently located for quick and easy 
equipment power connections 

 

Lighted main power indicator 

 

Attached 2-m (6-ft) input power cords 

 

Power cord retention and power cord labeling 

 

Modular PDU models 

To view the most recent modular PDU information, see the HP 

website (http://www.hp.com/go/rackandpower). 

From there, you can navigate to the appropriate page by following 

the steps below. 

1.

 

Click 

Power infrastructure.

 

2.

 

Click 

Power distribution units.

 

3.

 

Click

 Modular.

 

 

 

© Copyright 2006, 2008 Hewlett-Packard Development Company, L.P. 

The information contained herein is subject to change without notice. The only

warranties for HP products and services are set forth in the express warranty 

statements accompanying such products and services. Nothing herein should 

be construed as constituting an additional warranty. HP shall not be liable for 

technical or editorial errors or omissions contained herein. 

Part Number 240824-4 2 
October 2008 (Tenth Edition) 

 

0

Summary of Contents for 252663-B24 - PDU Power Distribution Strip

Page 1: ...ts circuit breakers move to Off position minimizing downtime Power cord retention Recessed handles to prevent inadvertent power off The extension bars if included provide the following features Multiple power outlets conveniently located for quick and easy equipment power connections Lighted main power indicator Attached 2 m 6 ft input power cords Power cord retention and power cord labeling Modul...

Page 2: ...ceed the total output rating marked on the mPDU WARNING To reduce the risk of personal injury from high leakage current verify earth connection before connecting the power supply The summation of input power for multiple pieces of information technology equipment through the use of power products can result in high leakage currents If the total system leakage current for a system of components exc...

Page 3: ...TL 4 8 4 40 6 252663 D74 NA JPN 0 0 0 6 252663 B33 INTL 0 0 0 6 252663 D75 NA JPN 0 0 0 6 252663 B34 INTL 0 0 0 6 AF500A 2 4 2 40 0 AF501A 2 4 2 40 0 AF511A 0 0 0 6 Model Number of extension bars Number of single double brackets Number of extension bar power cord retention bands Number of control unit tie wraps AF512A 0 0 0 6 AF513A 0 0 0 6 AF518A 0 0 0 6 AF519A 0 0 0 6 Required tools The followin...

Page 4: ...Installing the 0U brackets Installing the 1U brackets ...

Page 5: ... the rack when installing in a square holed rail Installing the control unit in a square and round holed rail NOTE Use the sheet metal mounting screws that are included with this kit when installing in a square and round holed rail Installing the extension bars if included The cord retention brackets are shown for clarification in the following diagrams though installation of the cord retention br...

Page 6: ...Installing the extension bars using single stick mounting brackets Connecting and securing the power cords ...

Page 7: ...n bars and control unit Control unit Total rating of control unit Outlet style Load CB rating Individual outlet rating 228481 001 24 A IEC 320 C19 15 A 12 A 228481 002 24 A IEC 320 C19 15 A 12 A 228481 003 32 A IEC 320 C19 15 A 12 A 228481 004 40 A IEC 320 C19 15 A 12 A 228481 006 16 A IEC 320 C19 10 A 8 A 228481 007 40 A IEC 320 C19 15 A 12 A 228481 008 40 A IEC 320 C19 15 A 12 A 435530 001 41 6 ...

Page 8: ......

Reviews: