Connecting the ground bonding
cable
NOTE:
This section is only applicable if a control unit was
shipped as part of your kit.
The ground bonding screw is provided as an attachment point for
conductors. Use a ground bonding cable if the rack contains any
conductors for the purpose of functional grounding or bonding of
ungrounded metal parts.
The ground bonding cable is not included in this kit.
Connecting the 16-A modular PDU
(model 252663-B24 WW) to the
power source
Hardwiring the 40-A modular PDU
The 40-A modular PDU (model 252663-B21 WW) must be
hardwired by a qualified electrician in accordance with local
electrical installation codes.
Connecting devices
When connecting devices, distribute the loads evenly to remain
within the capability of the extension bars and control unit.
Control
unit
Total rating of
control unit
Outlet
style
Load
CB
rating
Individual
outlet
rating
228481-
001
24 A
IEC 320-
C19
15 A
12 A
228481-
002
24 A
IEC 320-
C19
15 A
12 A
228481-
003
32 A
IEC 320-
C19
15 A
12 A
228481-
004
40 A
IEC 320-
C19
15 A
12 A
228481-
006
16 A
IEC 320-
C19
10 A
8 A
228481-
007
40 A
IEC 320-
C19
15 A
12 A
228481-
008
40 A
IEC 320-
C19
15 A
12 A
435530-
001
41.6 A
IEC 320-
C19
20 A
16 A
435530-
003
48 A
IEC 320-
C19
16 A
16 A
458745-
001
83.13 A
IEC 309-
C19
20 A
16 A
481337-
001
96 A
IEC 309-
C19
16 A
16 A
484168-
001
40 A
IEC 320-
C19
20 A
16 A
Extension
bar
Total rating of
extension bar
Outlet
style
Individual outlet
rating
411273-
001
16 A
NEMA 5-
15R
12 A
411273-
002
16 A
IEC 320-
C13
10 A
228480-
003
12 A
IEC 320-
C19
12 A
Checking the circuit breakers
If power to a device is interrupted, check the circuit breakers and
reset if necessary. If power is still not restored, contact your HP
authorized service representative.