Assembly of a CPU 41x–H
5.4 Mode switch
S7-400H
System Manual, 03/2012, A5E00267695-11
63
Data retained after a memory reset...
The following values are retained after a memory reset:
●
The content of the diagnostic buffer
If no FLASH card was inserted during memory reset, the CPU resets the capacity of the
diagnostic buffer to its default setting of 120 entries, i.e. the most recent 120 entries will
be retained in the diagnostic buffer.
You can read out the content of the diagnostic buffer using STEP 7.
●
The MPI/DP interface parameters. Note the special features shown in the table below.
–
MPI address
–
Highest MPI address
–
Baud rate.
●
Parameters of the PN interface. Note the special features shown in the table below.
–
Name (NameOfStation)
–
IP address of CPU
–
Subnet mask
–
Static SNMP parameters
●
The time of day
●
The status and value of the operating hours counter
Special feature
A special situation is presented for the MPI/DP and PN interface parameters when a memory
reset is preformed. The following parameters are valid after a memory reset:
●
Memory reset with inserted FLASH card:
The parameters stored on the FLASH card are valid
●
Memory reset without inserted FLASH card:
The parameters in the CPU are retained and valid.
Содержание SIMATIC S7-400H
Страница 24: ...Preface 1 1 Preface S7 400H 24 System Manual 03 2012 A5E00267695 11 ...
Страница 46: ...Getting Started 4 5 Special layout features of SIMATIC Manager S7 400H 46 System Manual 03 2012 A5E00267695 11 ...
Страница 120: ...Memory concept 10 1 Overview of the memory concept of S7 400H CPUs S7 400H 120 System Manual 03 2012 A5E00267695 11 ...
Страница 258: ...Communication 14 8 General issues regarding communication S7 400H 258 System Manual 03 2012 A5E00267695 11 ...
Страница 354: ...Synchronization modules 18 3 Selecting fiber optic cables S7 400H 354 System Manual 03 2012 A5E00267695 11 ...
Страница 434: ...Technical data 20 6 Runtimes of the FCs and FBs for redundant I Os S7 400H 434 System Manual 03 2012 A5E00267695 11 ...
Страница 460: ...Function modules and communication processors supported by the S7 400H S7 400H 460 System Manual 03 2012 A5E00267695 11 ...