S7-400 cycle and response times
19.2 Calculating the cycle time
S7-400H
362
System Manual, 03/2012, A5E00267695-11
Table 19- 6 Portion of the process image transfer time, CPU 417-5H
Portion
CPU 417–5H
stand-alone mode
CPU 417–5H
redundant
K
Base load
3 µs
4 µs
A
*)
In the central controller
Read/write byte/word/double word
7.3 µs
15 µs
B
*)
In the expansion unit with local link
Read/write byte/word/double word
20 µs
26 µs
C
*)**)
In the expansion unit with remote link
Read/write byte/word/double word
45 µs
50 µs
D1
In the DP area for the integrated DP interface
Read byte/word/double word
0.4 µs
10 µs
D2
***)
In the DP area for the external DP interfaces
Read/write byte/word/double word
5 µs
15 µs
E1
Consistent data in the process image for the integrated DP
interface
Read/write data
8 µs
30 µs
E2
Consistent data in the process image for the external DP
interface (CP 443–5 extended)
Read
write
80 µs
60 µs
100 µs
70 µs
F
In the PNIO area for the integrated PROFINET interface
Read/write for each byte/word/double word
2 µs
15 µs
G
Per submodule with 32 bytes of consistent data for the
integrated PROFINET interface
8 µs
30 µs
*)
In the case of I/O inserted into the central controller or expansion device,
the specified value contains the execution time of the I/O module
The module data is updated with the minimum number of accesses.
(example: 8 bytes result in 2 double word accesses; 16 bytes in 4 double word accesses.)
**)
Measured with IM460-3 and IM461-3 at a link length of 100 m
***)
Measured with modules with 1 byte of user data, e.g. DI 16.
Extending the cycle time
The calculated cycle time of a S7-400H CPU must be multiplied by a CPU-specific factor.
The table below lists these factors:
Table 19- 7 Extending the cycle time
Start-up 412–5H
stand-alone
mode
412–5H
redundant
414–5H
stand-alone
mode
414–5H
redundant
416–5H
stand-alone
mode
416–5H
redundant
417–5H
stand-alone
mode
417–5H
redundant
Factor
1.05
1.2
1.05
1.2
1.05
1.2
1.05
1.2
Long synchronization cables may increase cycle times This extension can have the factor 2 -
5 with a cable length of 10 km.
Содержание SIMATIC S7-400H
Страница 24: ...Preface 1 1 Preface S7 400H 24 System Manual 03 2012 A5E00267695 11 ...
Страница 46: ...Getting Started 4 5 Special layout features of SIMATIC Manager S7 400H 46 System Manual 03 2012 A5E00267695 11 ...
Страница 120: ...Memory concept 10 1 Overview of the memory concept of S7 400H CPUs S7 400H 120 System Manual 03 2012 A5E00267695 11 ...
Страница 258: ...Communication 14 8 General issues regarding communication S7 400H 258 System Manual 03 2012 A5E00267695 11 ...
Страница 354: ...Synchronization modules 18 3 Selecting fiber optic cables S7 400H 354 System Manual 03 2012 A5E00267695 11 ...
Страница 434: ...Technical data 20 6 Runtimes of the FCs and FBs for redundant I Os S7 400H 434 System Manual 03 2012 A5E00267695 11 ...
Страница 460: ...Function modules and communication processors supported by the S7 400H S7 400H 460 System Manual 03 2012 A5E00267695 11 ...