System modifications during operation
17.6 Removing components in STEP 7
S7-400H
System Manual, 03/2012, A5E00267695-11
313
17.6
Removing components in STEP 7
Starting situation
You have verified that the CPU parameters (e.g. monitoring times) match the planned new
program. Adapt the CPU parameters first, if necessary (see section Editing CPU parameters
(Page 323)).
The modules to be removed and their connected sensors and actuators are no longer of any
significance to the process being controlled. The fault-tolerant system is operating in
redundant system mode.
Procedure
Carry out the steps listed below to remove hardware components from a fault-tolerant
system in STEP 7. Details of each step are described in a subsection.
Step
What to do?
See section
1
Editing the hardware configuration offline
STEP 7, step 1: Editing the hardware
configuration offline (Page 314)
2
Editing and downloading the user program
STEP 7, step 2: Editing and downloading the
3
Stopping the reserve CPU
STEP 7, step 3: Stopping the reserve CPU
4
Downloading a new hardware configuration to the reserve
CPU
STEP 7, step 4: Downloading a new hardware
configuration to the reserve CPU (Page 316)
5
Switching to CPU with modified configuration
STEP 7, step 5: Switching to CPU with
modified configuration (Page 317)
6
Transition to redundant system mode
STEP 7, step 6: Transition to redundant
7
Modification of hardware
STEP 7, step 7: Modification of hardware
8
Editing and downloading organization blocks
Содержание SIMATIC S7-400H
Страница 24: ...Preface 1 1 Preface S7 400H 24 System Manual 03 2012 A5E00267695 11 ...
Страница 46: ...Getting Started 4 5 Special layout features of SIMATIC Manager S7 400H 46 System Manual 03 2012 A5E00267695 11 ...
Страница 120: ...Memory concept 10 1 Overview of the memory concept of S7 400H CPUs S7 400H 120 System Manual 03 2012 A5E00267695 11 ...
Страница 258: ...Communication 14 8 General issues regarding communication S7 400H 258 System Manual 03 2012 A5E00267695 11 ...
Страница 354: ...Synchronization modules 18 3 Selecting fiber optic cables S7 400H 354 System Manual 03 2012 A5E00267695 11 ...
Страница 434: ...Technical data 20 6 Runtimes of the FCs and FBs for redundant I Os S7 400H 434 System Manual 03 2012 A5E00267695 11 ...
Страница 460: ...Function modules and communication processors supported by the S7 400H S7 400H 460 System Manual 03 2012 A5E00267695 11 ...