Type of error
Cause of error
Response of the operating system
Error LED
Diagnostic
interrupt
An I/O module with interrupt capability
reports a diagnostic interrupt
In a configuration as of V6.0: The
synchronization module reports a
diagnostics interrupt; see chapter
Synchronization modules for S7–400H
(Page 341)
Call of OB 82
If the OB is not loaded: CPU changes
to STOP mode.
EXTF
Swapping interrupt Removal or insertion of an SM, and insertion
of a wrong module type.
Removing a synchronization module.
Call of OB 83
If the OB is not loaded: CPU changes
to STOP mode.
EXTF
Redundancy error
interrupt
Loss of redundancy on the CPUs
Standby master changeover
Synchronization error
Error in a synchronization module
Cancellation of the update process
Comparison error (e.g. RAM, PAA)
Call of OB 72
If the OB is not loaded: The CPU
remains in RUN.
EXTF
CPU hardware
fault
A memory error was detected and
eliminated
In a configuration older than V6.0: Data
transmission error at the redundant link.
Call of OB 84
If the OB is not loaded: The CPU
remains in RUN.
INTF
Program
execution error
Priority class is called, but the
corresponding OB is not available.
In the case of an SFB call: Missing or
faulty instance DB
Process image update error
Call of OB 85
If the OB is not loaded: CPU changes
to STOP mode.
INTF
EXTF
Failure of a
rack/station
Power failure in an expansion rack
Failure of a DP/PN segment
Failure of a coupling segment: Missing or
defective IM, interrupted cable
Call of OB 86
If the OB is not loaded: CPU changes
to STOP mode.
EXTF
Communication
error
Communication error:
Time synchronization
Access to DB when exchanging data via
communications function blocks
Call of OB 87
If the OB is not loaded: CPU does not
change to STOP mode.
INTF
Содержание SIMATIC S7-400H
Страница 24: ...Preface 1 1 Preface S7 400H 24 System Manual 03 2012 A5E00267695 11 ...
Страница 46: ...Getting Started 4 5 Special layout features of SIMATIC Manager S7 400H 46 System Manual 03 2012 A5E00267695 11 ...
Страница 120: ...Memory concept 10 1 Overview of the memory concept of S7 400H CPUs S7 400H 120 System Manual 03 2012 A5E00267695 11 ...
Страница 258: ...Communication 14 8 General issues regarding communication S7 400H 258 System Manual 03 2012 A5E00267695 11 ...
Страница 354: ...Synchronization modules 18 3 Selecting fiber optic cables S7 400H 354 System Manual 03 2012 A5E00267695 11 ...
Страница 434: ...Technical data 20 6 Runtimes of the FCs and FBs for redundant I Os S7 400H 434 System Manual 03 2012 A5E00267695 11 ...
Страница 460: ...Function modules and communication processors supported by the S7 400H S7 400H 460 System Manual 03 2012 A5E00267695 11 ...