S7-400 cycle and response times
19.8 Interrupt response time
S7-400H
380
System Manual, 03/2012, A5E00267695-11
Increasing the maximum interrupt response time with communication
The maximum interrupt response time is extended when the communication functions are
active. The additional time is calculated using the following formula:
CPU 41x–5H t
v
= 100 µs + 1000 µs × n%, significant extension possible
where n = cycle load due to communication
Signal modules
The process interrupt response time of signal modules is made up as follows:
●
Digital input modules
Process interrupt response time = internal interrupt processing time + input delay
You will find these times in the data sheet for the respective digital input module.
●
Analog input modules
Process interrupt response time = internal interrupt processing time + conversion time
The internal interrupt processing time for analog input modules can be neglected. The
conversion times can be found in the data sheet for the individual analog input modules.
The diagnostic interrupt response time of the signal modules is the time from detection of a
diagnostic event by the signal module to the triggering of the diagnostic interrupt by the
signal module. This short time can be neglected.
Hardware interrupt processing
Hardware interrupt processing begins when the process interrupt OB4x is called. Higher-
priority interrupts stop process interrupt processing. Direct access to I/O modules is
executed during the execution time of the operation. After the process interrupt has been
processed, the system either resumes cyclic program processing, or calls and processes
interrupt OBs of the same or lower priority.
Содержание SIMATIC S7-400H
Страница 24: ...Preface 1 1 Preface S7 400H 24 System Manual 03 2012 A5E00267695 11 ...
Страница 46: ...Getting Started 4 5 Special layout features of SIMATIC Manager S7 400H 46 System Manual 03 2012 A5E00267695 11 ...
Страница 120: ...Memory concept 10 1 Overview of the memory concept of S7 400H CPUs S7 400H 120 System Manual 03 2012 A5E00267695 11 ...
Страница 258: ...Communication 14 8 General issues regarding communication S7 400H 258 System Manual 03 2012 A5E00267695 11 ...
Страница 354: ...Synchronization modules 18 3 Selecting fiber optic cables S7 400H 354 System Manual 03 2012 A5E00267695 11 ...
Страница 434: ...Technical data 20 6 Runtimes of the FCs and FBs for redundant I Os S7 400H 434 System Manual 03 2012 A5E00267695 11 ...
Страница 460: ...Function modules and communication processors supported by the S7 400H S7 400H 460 System Manual 03 2012 A5E00267695 11 ...