Using I/Os in S7–400H
13.5 Other options for connecting redundant I/Os
S7-400H
212
System Manual, 03/2012, A5E00267695-11
Monitoring times during link-up and update
NOTICE
If you have made I/O modules redundant and have taken account of this in your program,
you may need to add an overhead to the calculated monitoring times so that no bumps
occur at output modules (in HW Config -> Properties CPU -> H Parameter).
An overhead is only required if you operate modules from the following table as redundant
modules.
Table 13- 8 For the monitoring times with redundant I/O
Module type
Overhead in ms
ET200M: Standard output modules
2
ET200M: HART output modules
10
ET200M: F output modules
50
ET200L–SC with analog outputs
≤ 80
ET200S with analog outputs or technology modules
≤ 20
Follow the steps below:
●
Calculate the overhead from the table. If you use several module types from the table
redundantly, apply the largest overhead.
●
Add this to all of the monitoring times calculated so far.
Содержание SIMATIC S7-400H
Страница 24: ...Preface 1 1 Preface S7 400H 24 System Manual 03 2012 A5E00267695 11 ...
Страница 46: ...Getting Started 4 5 Special layout features of SIMATIC Manager S7 400H 46 System Manual 03 2012 A5E00267695 11 ...
Страница 120: ...Memory concept 10 1 Overview of the memory concept of S7 400H CPUs S7 400H 120 System Manual 03 2012 A5E00267695 11 ...
Страница 258: ...Communication 14 8 General issues regarding communication S7 400H 258 System Manual 03 2012 A5E00267695 11 ...
Страница 354: ...Synchronization modules 18 3 Selecting fiber optic cables S7 400H 354 System Manual 03 2012 A5E00267695 11 ...
Страница 434: ...Technical data 20 6 Runtimes of the FCs and FBs for redundant I Os S7 400H 434 System Manual 03 2012 A5E00267695 11 ...
Страница 460: ...Function modules and communication processors supported by the S7 400H S7 400H 460 System Manual 03 2012 A5E00267695 11 ...