Stand-alone operation
S7-400H
448
System Manual, 03/2012, A5E00267695-11
What you have to take into account for stand-alone operation of a fault-tolerant CPU
NOTICE
When operating a fault-tolerant CPU in stand-alone mode, no synchronization modules
may be connected. The rack number must be set to "0".
Although a fault-tolerant CPU has additional functions compared to a standard S7-400 CPU,
it does not support specific functions. So particularly when programming your automation
system, you need to know the CPU on which you are going to run the user program. A user
program written for a standard S7-400 CPU usually will not run on a fault-tolerant CPU in
stand-alone mode without adaptations.
The table below lists the differences between the operation of a fault-tolerant CPU in stand-
alone mode and in redundant mode.
Table B-1 Differences between stand-alone mode and redundant mode
Function
Fault-tolerant CPU in stand-alone mode
Fault-tolerant CPU in redundant system
mode
Connection of S5 modules via IM
or adapter casing
via IM 463–2
No
Redundancy error OBs (OB 70,
OB 72)
Yes, but no calls
Yes
CPU hardware fault
(OB 84)
after the detection and elimination of
memory errors
after the detection and elimination of
memory errors
with reduced performance of the
redundant link between the two CPUs
SSL ID W#16#0232 index
W#16#0004 byte 0 of the "index"
word in the data record
W#16#F8
Single mode: W#16#F8 or W#16#F9
Redundant:
W#16#F8 and W#16#F1 or
W#16#F9 and W#16#F0
Multi-DP master mode
Yes
No
System modifications during
operation
Yes, as described in the "System
Modification during Operation Using CIR"
manual.
Yes, as described in chapter Failure and
replacement of components during
operation (Page 265) for redundant
operation.
Содержание SIMATIC S7-400H
Страница 24: ...Preface 1 1 Preface S7 400H 24 System Manual 03 2012 A5E00267695 11 ...
Страница 46: ...Getting Started 4 5 Special layout features of SIMATIC Manager S7 400H 46 System Manual 03 2012 A5E00267695 11 ...
Страница 120: ...Memory concept 10 1 Overview of the memory concept of S7 400H CPUs S7 400H 120 System Manual 03 2012 A5E00267695 11 ...
Страница 258: ...Communication 14 8 General issues regarding communication S7 400H 258 System Manual 03 2012 A5E00267695 11 ...
Страница 354: ...Synchronization modules 18 3 Selecting fiber optic cables S7 400H 354 System Manual 03 2012 A5E00267695 11 ...
Страница 434: ...Technical data 20 6 Runtimes of the FCs and FBs for redundant I Os S7 400H 434 System Manual 03 2012 A5E00267695 11 ...
Страница 460: ...Function modules and communication processors supported by the S7 400H S7 400H 460 System Manual 03 2012 A5E00267695 11 ...