System modifications during operation
17.7 Editing CPU parameters
S7-400H
System Manual, 03/2012, A5E00267695-11
325
17.7.2
Step 1: Editing CPU parameters offline
Starting situation
The fault-tolerant system is operating in redundant system mode.
Procedure
1.
Edit the relevant CPU properties offline in HW Config.
2.
Compile the new hardware configuration, but do not load it into the target system just yet.
Result
The modified hardware configuration is in the PG/ES. The target system continues operation
with the old configuration in redundant system mode.
17.7.3
Step 2: Stopping the reserve CPU
Starting situation
The fault-tolerant system is operating in redundant system mode.
Procedure
1.
In SIMATIC Manager, select a CPU of the fault-tolerant system, then choose "PLC >
Operating Mode" from the menu.
2.
In the "Operating Mode" dialog box, select the reserve CPU, then click "Stop".
Result
The reserve CPU switches to STOP mode, the master CPU remains in RUN mode, the fault-
tolerant system works in single mode. The one-sided I/O of the reserve CPU is no longer
addressed.
Содержание SIMATIC S7-400H
Страница 24: ...Preface 1 1 Preface S7 400H 24 System Manual 03 2012 A5E00267695 11 ...
Страница 46: ...Getting Started 4 5 Special layout features of SIMATIC Manager S7 400H 46 System Manual 03 2012 A5E00267695 11 ...
Страница 120: ...Memory concept 10 1 Overview of the memory concept of S7 400H CPUs S7 400H 120 System Manual 03 2012 A5E00267695 11 ...
Страница 258: ...Communication 14 8 General issues regarding communication S7 400H 258 System Manual 03 2012 A5E00267695 11 ...
Страница 354: ...Synchronization modules 18 3 Selecting fiber optic cables S7 400H 354 System Manual 03 2012 A5E00267695 11 ...
Страница 434: ...Technical data 20 6 Runtimes of the FCs and FBs for redundant I Os S7 400H 434 System Manual 03 2012 A5E00267695 11 ...
Страница 460: ...Function modules and communication processors supported by the S7 400H S7 400H 460 System Manual 03 2012 A5E00267695 11 ...