S7-400 cycle and response times
19.2 Calculating the cycle time
S7-400H
System Manual, 03/2012, A5E00267695-11
363
Operating system execution time at the cycle control point
The table below shows the operating system execution time at the cycle checkpoint of the
CPUs.
Table 19- 8 Operating system execution time at the cycle control point
Sequence 412-5H
stand-alone
mode
412–5H
redundant
414-5H
stand-alone
mode
414–5H
redundant
416–5H
stand-alone
mode
416–5H
redundant
417-5H
stand-alone
mode
417–5H
redundant
Cycle
control at
the SCCP
120-700 µs
∅ 130 µs
405-
2080 µs
∅ 505 µs
70-450 µs
∅ 80 µs
260-
1350 µs
∅ 310 µs
50-400 µs
∅ 55
180-970 µs
∅ 215
30 - 330 µs
∅ 35 µs
115 -
650 µs
∅ 130 µs
Extended cycle time due to nested interrupts
Table 19- 9 Extended cycle time due to nested interrupts
CPU
Hardware
interrupt
Diagnostic
interrupt
Time-of-
day
interrupt
Delay interrupt
Cyclic
inter-
rupt
Programming
error
I/O
access
error
Asyn-
chronous
error
CPU 412-5H
stand-alone
mode
240 µs
240 µs
230 µs
150 µs
150 µs 80 µs
80 µs
180 µs
CPU 412–5H
redundant
680 µs
550 µs
700 µs
580 µs
450 µs 350 µs
179 µs
550 µs
CPU 414–5H
stand-alone
mode
160 µs
120 µs
150 µs
100 µs
100 µs 60 µs
60 µs
120 µs
CPU 414–5H
redundant
420 µs
400 µs
490 µs
360 µs
280 µs 220 µs
120 µs
306 µs
CPU 416–5H
stand-alone
mode
120 µs
110 µs
100 µs
80 µs
60 µs
40 µs
40 µs
80 µs
CPU 416–5H
redundant
300 µs
250 µs
370 µs
220 µs
200 µs 150 µs
90 µs
230 µs
CPU 417–5H
stand-alone
mode
90 µs
70 µs
70 µs
50 µs
50 µs
30 µs
30 µs
70 µs
CPU 417–5H
redundant
200 µs
170 µs
230 µs
150 µs
150 µs 100 µs
45 µs
133 µs
The program runtime at interrupt level must be added to this time extension.
The corresponding times are added together if the program contains nested interrupts.
Содержание SIMATIC S7-400H
Страница 24: ...Preface 1 1 Preface S7 400H 24 System Manual 03 2012 A5E00267695 11 ...
Страница 46: ...Getting Started 4 5 Special layout features of SIMATIC Manager S7 400H 46 System Manual 03 2012 A5E00267695 11 ...
Страница 120: ...Memory concept 10 1 Overview of the memory concept of S7 400H CPUs S7 400H 120 System Manual 03 2012 A5E00267695 11 ...
Страница 258: ...Communication 14 8 General issues regarding communication S7 400H 258 System Manual 03 2012 A5E00267695 11 ...
Страница 354: ...Synchronization modules 18 3 Selecting fiber optic cables S7 400H 354 System Manual 03 2012 A5E00267695 11 ...
Страница 434: ...Technical data 20 6 Runtimes of the FCs and FBs for redundant I Os S7 400H 434 System Manual 03 2012 A5E00267695 11 ...
Страница 460: ...Function modules and communication processors supported by the S7 400H S7 400H 460 System Manual 03 2012 A5E00267695 11 ...