Assembly of a CPU 41x–H
5.6 Using memory cards
S7-400H
System Manual, 03/2012, A5E00267695-11
67
5.6
Using memory cards
Types of memory cards for the S7–400
Two types of memory cards are used for S7–400H:
●
RAM cards
●
FLASH cards
What type of memory card should I use?
Whether you use a RAM card or a FLASH card depends on your application.
Table 5- 5
Types of memory card
If you ...
then ...
want to be able to edit your program in RUN
mode,
use a RAM card
want to keep a permanent backup of your user
program on the memory card, even when power
is off, i.e. without backup or outside the CPU,
use a FLASH card
RAM card
Insert the RAM card to load the user program in the CPU. Load the user program in STEP 7
by selecting "Target system > Download".
You can load the entire user program or individual elements such as FBs, FCs, OBs, DBs, or
SDBs in the load memory in STOP or RUN mode.
When you remove the RAM card from the CPU, the information stored on it will be lost. The
RAM card is not equipped with an integrated backup battery.
If the power supply is equipped with an operational backup battery, or the CPU is supplied
with an external backup voltage at the "EXT. BATT." socket, the RAM card memory contents
are retained when power is switched off, provided the RAM card remains inserted in the
CPU and the CPU remains inserted in the rack.
Содержание SIMATIC S7-400H
Страница 24: ...Preface 1 1 Preface S7 400H 24 System Manual 03 2012 A5E00267695 11 ...
Страница 46: ...Getting Started 4 5 Special layout features of SIMATIC Manager S7 400H 46 System Manual 03 2012 A5E00267695 11 ...
Страница 120: ...Memory concept 10 1 Overview of the memory concept of S7 400H CPUs S7 400H 120 System Manual 03 2012 A5E00267695 11 ...
Страница 258: ...Communication 14 8 General issues regarding communication S7 400H 258 System Manual 03 2012 A5E00267695 11 ...
Страница 354: ...Synchronization modules 18 3 Selecting fiber optic cables S7 400H 354 System Manual 03 2012 A5E00267695 11 ...
Страница 434: ...Technical data 20 6 Runtimes of the FCs and FBs for redundant I Os S7 400H 434 System Manual 03 2012 A5E00267695 11 ...
Страница 460: ...Function modules and communication processors supported by the S7 400H S7 400H 460 System Manual 03 2012 A5E00267695 11 ...