Assembly of a CPU 41x–H
5.4 Mode switch
S7-400H
64
System Manual, 03/2012, A5E00267695-11
5.4.3
Cold restart / Warm restart
Cold restart
●
A cold restart resets the process image, all bit memories, timers, counters, and data
blocks to the initial values stored in the load memory, regardless of whether these data
were parameterized as being retentive or not.
●
Program execution resumes with OB 1, or with OB 102 if available.
Restart (warm restart)
●
A warm restart resets the process image and the non-retentive bit memories, timers,
times, and counters.
Retentive bit memories, timers, counters, and all data blocks retain their last valid value.
●
The associated startup OB is OB 100
●
Program execution resumes with OB 1, or with OB 100 if available.
●
If the power supply is interrupted, the warm restart function is only available in backup
mode.
Note
Restart in buffered Power On mode
In buffered PowerOn mode of a fault-tolerant system with large configurations, many CPs
and/or external DP masters, it may take up to 30 seconds until a requested restart is
executed.
Operating sequence for warm restart
1.
Set the switch to the STOP position.
Result: The STOP LED lights up.
2.
Set the switch to RUN.
Result: The STOP LED goes dark, the RUN LED is lit.
Operating sequence for cold restart
You can only initiate a cold restart using the programming device command "Cold restart".
For this purpose, the CPU must be in STOP mode and the mode switch must be set to RUN.
Содержание SIMATIC S7-400H
Страница 24: ...Preface 1 1 Preface S7 400H 24 System Manual 03 2012 A5E00267695 11 ...
Страница 46: ...Getting Started 4 5 Special layout features of SIMATIC Manager S7 400H 46 System Manual 03 2012 A5E00267695 11 ...
Страница 120: ...Memory concept 10 1 Overview of the memory concept of S7 400H CPUs S7 400H 120 System Manual 03 2012 A5E00267695 11 ...
Страница 258: ...Communication 14 8 General issues regarding communication S7 400H 258 System Manual 03 2012 A5E00267695 11 ...
Страница 354: ...Synchronization modules 18 3 Selecting fiber optic cables S7 400H 354 System Manual 03 2012 A5E00267695 11 ...
Страница 434: ...Technical data 20 6 Runtimes of the FCs and FBs for redundant I Os S7 400H 434 System Manual 03 2012 A5E00267695 11 ...
Страница 460: ...Function modules and communication processors supported by the S7 400H S7 400H 460 System Manual 03 2012 A5E00267695 11 ...