System modifications during operation
17.8 Changing the CPU memory configuration
S7-400H
System Manual, 03/2012, A5E00267695-11
333
Inserting the Flash card
Proceed as follows:
1.
Set the reserve CPU to STOP and insert the FLASH Card into the CPU.
2.
Reset the CPU using STEP 7.
3.
Download the program data with the STEP 7 "Download User Program to Memory Card"
command. Note: Select the correct CPU from the selection dialog.
4.
Switch to the CPU with the changed configuration using the "Operating Mode" dialog.
This changes over the master/reserve roles; the CPU with the Flash Card is now the
master CPU. The reserve CPU is now in STOP.
5.
Next, insert the Flash Card in the CPU that is in STOP. Reset the CPU using STEP 7.
6.
Carry out step 4: Download the program data with the STEP 7 "Download User Program
to Memory Card" command. Note: Select the correct CPU from the selection dialog.
7.
Execute a warm restart of the reserve CPU using the "Operating Mode" dialog. The
system status now changes to "Redundant" mode.
Removing the FLASH card
The online and offline data consistency described earlier also applies when you remove
FLASH Cards from a fault-tolerant system. In addition, the available RAM size must not be
less than the actual size of the STEP 7 program (STEP 7 Program > Block Container >
"Blocks" Properties).
1.
Set the reserve CPU to STOP and remove the FLASH Card. Adapt the memory
configuration as required.
2.
Reset the CPU using STEP 7.
3.
Download the block container using STEP 7.
4.
Switch to the CPU with the changed configuration using the "Operating Mode" dialog.
5.
Remove the FLASH Card from the CPU which is now in STOP. Adapt the RAM
configuration as required, and then perform a CPU memory reset.
6.
Execute a warm restart of the reserve CPU using the "Operating Mode" dialog. The
system status now changes to "Redundant" mode.
Содержание SIMATIC S7-400H
Страница 24: ...Preface 1 1 Preface S7 400H 24 System Manual 03 2012 A5E00267695 11 ...
Страница 46: ...Getting Started 4 5 Special layout features of SIMATIC Manager S7 400H 46 System Manual 03 2012 A5E00267695 11 ...
Страница 120: ...Memory concept 10 1 Overview of the memory concept of S7 400H CPUs S7 400H 120 System Manual 03 2012 A5E00267695 11 ...
Страница 258: ...Communication 14 8 General issues regarding communication S7 400H 258 System Manual 03 2012 A5E00267695 11 ...
Страница 354: ...Synchronization modules 18 3 Selecting fiber optic cables S7 400H 354 System Manual 03 2012 A5E00267695 11 ...
Страница 434: ...Technical data 20 6 Runtimes of the FCs and FBs for redundant I Os S7 400H 434 System Manual 03 2012 A5E00267695 11 ...
Страница 460: ...Function modules and communication processors supported by the S7 400H S7 400H 460 System Manual 03 2012 A5E00267695 11 ...