Communication
14.1 Communication services
S7-400H
226
System Manual, 03/2012, A5E00267695-11
14.1.8
SNMP network protocol
Availability
S7-400H CPUs as of firmware version 6.0 support the SNMP network protocol. The CPUs
must also be configured in this or a higher firmware version for this.
Properties
SNMP (Simple Network Management Protocol) is the standardized protocol for diagnostics
of the Ethernet network infrastructure. In the office setting and in automation engineering,
devices from many different manufacturers support SNMP on the Ethernet. SNMP-based
applications can be operated on the same network in parallel to applications with
PROFINET.
Configuration of the SNMP OPC server is integrated in the STEP 7 Hardware Configuration
application. Already configured S7 modules from the STEP 7 project can be transferred
directly. As an alternative to STEP 7, you can also perform the configuration with the NCM
PC (included on the SIMATIC NET CD). All Ethernet devices can be detected by means of
their IP address and/or the SNMP protocol (SNMP V1) and transferred to the configuration.
Use the profile MIB_II_V10.
Applications based on SNMP can be operated on the same network at the same time as
applications with PROFINET.
Note
MAC addresses
During SNMP diagnostics, the following MAC addresses are shown for the ifPhysAddress
parameter as of FW V5.1:
Interface 1 (PN interface) = MAC address (specified on the front panel of the CPU)
Interface 2 (port 1) = MAC a 1
Interface 3 (port 2) = MAC a 2
Diagnostics with SNMP OPC Server in SIMATIC NET
The SNMP OPC server software provides diagnostics and configuration functions for all
SNMP devices. The OPC server uses the SNMP protocol to perform data exchange with
SNMP devices.
All information can be integrated in OPC-compatible systems, such as the WinCC HMI
system. This enables process and network diagnostics to be combined in the HMI system.
Reference
For further information on the SNMP communication service and diagnostics with SNMP,
refer to the
PROFINET System Description.
Содержание SIMATIC S7-400H
Страница 24: ...Preface 1 1 Preface S7 400H 24 System Manual 03 2012 A5E00267695 11 ...
Страница 46: ...Getting Started 4 5 Special layout features of SIMATIC Manager S7 400H 46 System Manual 03 2012 A5E00267695 11 ...
Страница 120: ...Memory concept 10 1 Overview of the memory concept of S7 400H CPUs S7 400H 120 System Manual 03 2012 A5E00267695 11 ...
Страница 258: ...Communication 14 8 General issues regarding communication S7 400H 258 System Manual 03 2012 A5E00267695 11 ...
Страница 354: ...Synchronization modules 18 3 Selecting fiber optic cables S7 400H 354 System Manual 03 2012 A5E00267695 11 ...
Страница 434: ...Technical data 20 6 Runtimes of the FCs and FBs for redundant I Os S7 400H 434 System Manual 03 2012 A5E00267695 11 ...
Страница 460: ...Function modules and communication processors supported by the S7 400H S7 400H 460 System Manual 03 2012 A5E00267695 11 ...