Failure and replacement of components during operation
16.3 Failure and replacement of components of the distributed I/Os
S7-400H
278
System Manual, 03/2012, A5E00267695-11
16.3.3
Failure and replacement of a PROFIBUS DP slave
Starting situation
Failure
How does the system react?
The S7-400H is in redundant system mode and a
DP slave fails.
Both CPUs report the event in the diagnostic
buffer and via the appropriate OB.
Procedure
Proceed as follows to replace a DP slave:
Step
What has to be done?
How does the system react?
1
Turn off the supply for the DP slave.
–
2
Remove the bus connector.
–
3
Replace the DP slave.
–
4
Plug the bus connector back in and turn the
power supply back on.
The CPUs process the rack failure OB
86 synchronized with each other
(outgoing event)
The associated DP master can address
the DP slave.
16.3.4
Failure and replacement of PROFIBUS DP cables
Starting situation
Failure
How does the system react?
The S7-400H is in redundant system mode and
the PROFIBUS DP cable is defective.
With single-channel one-sided I/O:
Rack failure OB (OB 86) is started (incoming
event). The DP master can no longer process
connected DP slaves
(station failure).
With switched I/O:
I/O redundancy error OB (OB 70) is started
(incoming event). DP slaves are addressed
via the DP master of the partner.
Содержание SIMATIC S7-400H
Страница 24: ...Preface 1 1 Preface S7 400H 24 System Manual 03 2012 A5E00267695 11 ...
Страница 46: ...Getting Started 4 5 Special layout features of SIMATIC Manager S7 400H 46 System Manual 03 2012 A5E00267695 11 ...
Страница 120: ...Memory concept 10 1 Overview of the memory concept of S7 400H CPUs S7 400H 120 System Manual 03 2012 A5E00267695 11 ...
Страница 258: ...Communication 14 8 General issues regarding communication S7 400H 258 System Manual 03 2012 A5E00267695 11 ...
Страница 354: ...Synchronization modules 18 3 Selecting fiber optic cables S7 400H 354 System Manual 03 2012 A5E00267695 11 ...
Страница 434: ...Technical data 20 6 Runtimes of the FCs and FBs for redundant I Os S7 400H 434 System Manual 03 2012 A5E00267695 11 ...
Страница 460: ...Function modules and communication processors supported by the S7 400H S7 400H 460 System Manual 03 2012 A5E00267695 11 ...